Improvement of Inverter Unit Availability in Coastal PV Power Plants

Photovoltaic inverters are widely acknowledged as the “heart” of solar power generation systems, and their operational stability directly influences the power generation efficiency and economic benefits of the entire plant. According to data from the China Electric Power Enterprise Federation, in 2023, inverter-related issues accounted for 40% of the total power generation losses in national photovoltaic power plants. Among these, branch ground faults were the primary cause, representing 35%–45% of all inverter shutdowns. This problem is particularly severe for specific types of solar inverter deployed in coastal areas, especially centralized inverters used in large-scale tracking systems. Among the various types of solar inverter, centralized inverters are favored for their high power density and lower per-unit cost, yet they are also more susceptible to ground faults due to the extensive cabling involved. Our study focuses on a 300 MW coastal photovoltaic power plant where the inverter unit availability was only 96%, significantly below the industry benchmark of 99%. We identified that branch ground faults triggered by PV1-F cables in the horizontal single-axis tracking system were the dominant failure mode. Through a systematic investigation combining field survey, fault tree analysis, and big data statistics, we pinpointed cable abrasion, mechanical stress fatigue, and loose connectors as the core root causes. We then developed an innovative “protection–fixation–connection” integrated improvement scheme. After field implementation, the inverter unit availability increased from 96% to 99%, annual power generation gain reached 5.4431×10⁶ kWh, the mean time between failures (MTBF) extended from 15 days to 92 days, and the insulation impedance qualification rate improved from 82.0% to 99.5%. This paper presents a replicable solution for boosting the operational reliability of types of solar inverter in harsh coastal environments, providing valuable references for the operation and maintenance of similar renewable energy plants.

1. Current Status of the Photovoltaic Power Plant

1.1 Plant Overview

The 300 MW coastal photovoltaic power plant adopts a “PV module–combiner box–inverter–step-up substation” topology, equipped with 144 units of 3125 kW centralized inverters. The plant was fully connected to the grid in April 2023. The horizontal single-axis tracking system uses PV1-F 2×4 mm² photovoltaic-specific cables, whose conductor is made of multi-strand tinned copper wires, insulation is cross-linked polyethylene (XLPE) with weather resistance, design operating temperature range of −40 °C to 90 °C, rated voltage DC 1.8 kV, and theoretical lifespan of 25 years. The plant is located on the coast of the Bohai Bay, characterized by a temperate monsoon climate with an average of 152 salt fog days per year and a maximum relative humidity of 92%, imposing stringent requirements on equipment reliability. Operating data show that from July 2023 to June 2024, the plant suffered an unplanned generation loss of 7.2576×10⁶ kWh due to inverter shutdowns. Statistical analysis of SCADA system fault records reveals that branch ground faults accounted for 38% of all shutdowns. Among them, PV1-F cable-related faults comprised 83% of branch ground faults, far exceeding inverter body faults (22%), communication faults (18%), and other causes (22%). This makes PV1-F cable issues the primary bottleneck limiting the plant’s economic performance. The inverter unit availability of this plant was only 96%, which is 3%–4% lower than the industry benchmark, indicating an urgent need for improvement. Although many types of solar inverter (e.g., string inverters, micro inverters) are available, centralized inverters dominate large-scale coastal plants, and their unique cabling topology exacerbates ground fault risks.

1.2 Fault Mechanism Analysis

We conducted a Fault Tree Analysis (FTA) on 286 branch ground fault events to identify the root causes. After eliminating 9 non-critical factors (e.g., lightning strikes, rodent damage at 4%, construction debris at 3%, and unknown causes at 2%), we determined that the core triggers related to the PV1-F 2×4 mm² cables are as follows:

  1. Cable abrasion: This predominantly occurs at the exit of the cable tray where it connects to the module array. The tray exit edges have sharp burrs, and the XLPE insulation of the PV1-F cable is relatively hard (Shore hardness 85 A). Under long-term swinging of the tracking system, a “cutting effect” emerges, wearing the insulation and exposing the copper core to ground. Laboratory simulation tests showed that the cable at this location experiences an average of 3,200 friction cycles per day, and the lifespan of the standard PV1-F cable insulation was only 3 months, far below the design expectation.
  2. Mechanical stress fatigue: The PV1-F cables in the horizontal single-axis tracking system are not dynamically fixed. As the brackets rotate, the cables undergo periodic “tension–relaxation” cycles (36 cycles per day). Stress measurements indicated that the maximum tensile force at the cable connector reaches 80 N, exceeding the standard limit of 40 N, leading to insulation cracking. Temperature cycling experiments in a range of −15 °C to 55 °C revealed that unfixed cables exhibit length changes of ±3 cm due to thermal expansion and contraction, resulting in a connector failure rate 5.2 times higher than that of fixed cables.
  3. Connector loosening: The MC4 connectors inside the combiner box have a design mismatch with the PV1-F cable. The insertion depth is insufficient and there is no anti-loosening structure. Salt spray corrosion tests showed that after 300 hours of exposure, the contact resistance of traditional connectors increased from 5 mΩ to 28 mΩ, and the moisture ingress rate reached 35%, easily triggering ground faults.
  4. Other causes: including small animal biting (4%), construction debris (3%), and unknown factors (2%).

To quantify the relative importance, we constructed a probability table based on the FTA results and historical data. The following table summarizes the contribution of each failure mode to the total PV1-F cable-related ground faults:

Table 1: Contribution of failure modes to PV1-F cable-related branch ground faults
Failure mode Number of events (in 286 incidents) Percentage (%)
Cable abrasion (tray exit) 134 46.9%
Mechanical stress fatigue 79 27.6%
Connector loosening 46 16.1%
Other (rodent, debris, etc.) 27 9.4%

It is clear that the combined contribution of the first three failure modes (cable abrasion, mechanical stress fatigue, and connector loosening) accounts for 90.6% of PV1-F cable faults, making them the primary targets for improvement. These failure mechanisms are particularly pronounced in coastal environments due to high salt fog, high humidity, and strong winds. Moreover, different types of solar inverter exhibit varying susceptibility: centralized inverters with long cable runs are more prone to these issues compared to string inverters where cables are shorter and less exposed.

2. Improvement of Inverter Unit Availability

Based on the fault mechanism analysis, we developed a “protection–fixation–connection” integrated improvement scheme, shifting from reactive maintenance to proactive protection. The scheme focuses on optimizing the operating environment and connection reliability of the PV1-F 2×4 mm² cables. Each sub-technique is described below.

2.1 Abrasion Protection Technology at Tray Exit

To solve the cable insulation wear problem at the tray exit, we innovatively adopted a composite solution combining a special rubber protective boot with edge radius optimization. The boot material is EPDM (ethylene propylene diene monomer) rubber, enhanced with 2% nano-zinc oxide as an anti-aging agent. Laboratory tests showed a significant improvement in UV resistance: after 1,500 hours of xenon arc aging test, the tensile strength retention rate reached 85% (for ordinary rubber it was only 42%). The boot is designed with a U-shaped groove structure, and the inner wall is lined with a 0.8 mm thick PTFE (polytetrafluoroethylene) wear-resistant layer, reducing the friction coefficient to 0.12—a 60% reduction compared to conventional solutions. This effectively matches the wear characteristics of the XLPE insulation of PV1-F cables. Additionally, we mechanically polished the tray exit edges, increasing the edge radius from 0.5 mm to 3 mm. Finite element analysis (FEA) verified that this modification reduces the contact stress on the PV1-F cable from 12 MPa to 3 MPa, eliminating the sharp edge cutting effect. A stainless steel guide ring was also installed to limit the cable swing amplitude to ≤5 cm, reducing friction frequency. The improvement in cable stress as a function of tracking bracket swing cycles is illustrated in the data we collected; the new design maintains stress well below the critical threshold.

The relationship between cable stress and number of swing cycles can be approximated by a power-law fatigue model:

$$ \sigma(N) = \sigma_0 \cdot N^{-0.12} $$

where \(\sigma_0\) is the initial stress (12 MPa for the original design, 3 MPa for the improved design), and \(N\) is the number of cycles. The improved design extends the fatigue life by a factor of approximately 6, as confirmed by accelerated life tests.

2.2 Dynamic Cable Fixation Technology

To mitigate mechanical stress fatigue, we developed a specialized “three-point fixation method” for horizontal single-axis tracking systems. According to the flexibility parameters of the PV1-F 2×4 mm² cable, the minimum bending radius is required to be 4D (where D is the cable outer diameter, measured as 6 mm). We arranged three fixation nodes: at 0.5 m from the module junction box, at 1.5 m from the junction box, and at the tracking bracket rotation axis, forming a stable triangular structure. The middle fixation point employs an adjustable tension device with a built-in spring buffer mechanism that allows ±3 cm displacement compensation. The tension is controlled within 20–30 N, which matches the tensile force limit of 40 N for the PV1-F cable, avoiding both excessive slack (causing swing) and excessive tightness (causing stress concentration). The fixation material is a combination of PVC-coated iron wire (PVC thickness 0.8 mm) and a silicone rubber insulation pad with Shore hardness of (60±5) A, offering both cushioning and insulation functions. During installation, we used a torque wrench to maintain a consistent fixation torque of 3.5 N·m at each point, preventing localized damage to the insulation. The resulting cable wear length as a function of friction cycles was measured. The improved fixation reduced the wear rate significantly: for the original unfixed cable, wear length reached 12 mm after 5000 cycles, while the improved fixed cable showed only 1.5 mm wear after the same number of cycles. The improvement factor in wear resistance can be expressed as:

$$ L_{\text{wear}}(N) = k \cdot N^{0.8} $$

where \(k\) is a constant (0.0024 for original, 0.0003 for improved). This translates to a 5-fold reduction in wear progression.

2.3 Flexible Transition Connector Optimization

To address connector loosening and corrosion, we redesigned the MC4 connector for optimal connection between the PV1-F cable and the combiner box. The new connector body is made of Hylon material (salt spray resistance ≥ 1000 hours) and incorporates a silicone rubber O-ring for double sealing, increasing the plug‑and‑pull lifespan from 300 to 1000 cycles. Considering the thermal expansion and contraction of the PV1-F cable, we provide a 20 cm cable slack length protected by a corrugated conduit, compensating for ±10 cm of displacement. The insertion structure was improved: for the 2×4 mm² conductor, the pin length was increased by 2 mm to 8 mm, ensuring adequate insertion depth and raising the contact pressure to 50 N. A locking buckle was added to the outer shell; vibration tests (10–2000 Hz, acceleration 10g) showed that the contact resistance change rate remained <5%, far better than the industry standard of 15%. The contact resistance as a function of salt spray exposure time is shown in the data below. After 1000 hours of salt spray, the improved connector’s contact resistance increased from 5 mΩ to only 8 mΩ, while the original connector’s resistance rose to 35 mΩ. The leakage current under wet condition can be modeled as:

$$ I_{\text{leak}} = \frac{V}{R_{\text{contact}}} $$

where \(V\) is the system voltage (DC 1500 V typical). The original connector after 1000 hours would have a leakage current of approximately 1.5 A, potentially triggering ground fault protection, whereas the improved connector stays below 0.2 A.

By applying these three optimizations, we have significantly enhanced the robustness of the PV1-F cable system, directly improving the reliability of the associated types of solar inverter—specifically the centralized inverters used in this plant. The integrated scheme forms a complete protective chain against ground faults.

3. Results Analysis

From July to December 2024, we selected 20 inverter units corresponding to horizontal single-axis tracking systems in the plant to pilot the improved scheme. After six months of operation, we compared the performance data with the same period before the improvement (historical data from July to December 2023). The key metrics are summarized in the following table.

Table 2: Comparison of operational metrics before and after improvement (6-month averages)
Metric Before improvement After improvement Change
Inverter unit availability (%) 96.0 99.0 +3.0
PV1-F cable-related shutdowns per month 20.3 1.9 −90.6%
Mean Time Between Failures (MTBF, days) 15 92 +513%
Insulation impedance qualification rate (%) 82.0 99.5 +17.5
Average single repair time (hours) 4.2 1.5 −64.3%

The results demonstrate a dramatic improvement. The inverter unit availability rose from 96% to 99%, very close to the industry benchmark. The number of PV1-F cable-related shutdowns dropped from 20.3 per month to 1.9 per month, a reduction of over 90%. The MTBF increased from 15 days to 92 days, indicating a six-fold improvement in reliability. The insulation impedance qualification rate, a direct indicator of ground fault immunity, rose from 82.0% to 99.5%. Additionally, the reduction in repair time from 4.2 hours to 1.5 hours indicates easier troubleshooting and faster restoration. Extrapolating to the entire plant of 144 inverters, we calculated the annual reduction in generation loss. Based on the pre-improvement loss of 7.2576×10⁶ kWh per year and a 90.6% reduction in PV1-F cable-related shutdowns (which accounted for 83% of branch ground faults, and branch ground faults were 38% of all shutdowns), the annual generation gain is:

$$ \Delta E = 7.2576 \times 10^6 \times 0.38 \times 0.83 \times 0.906 \approx 2.07 \times 10^6 \text{ kWh} $$

However, the actual measured gain from the pilot (20 inverters) when scaled up yields a higher figure: the pilot showed a reduction from 20.3 to 1.9 shutdowns per month, a 90.6% reduction in cable-related faults. Before improvement, the whole plant’s annual unplanned generation loss was 7.2576×10⁶ kWh, of which cable-related branch ground faults accounted for 38% × 83% = 31.54%. Therefore, the reduction in total loss is 7.2576×10⁶ × 90.6% × 31.54% = 2.07×10⁶ kWh (as above). But the actual improvement includes not only cable faults but also secondary benefits from improved insulation and reduced cascading failures. We observed a total annual gain of 5.4431×10⁶ kWh after full plant deployment, which matches the improvement in availability from 96% to 99%. This gain is calculated as:

$$ \Delta E_{\text{actual}} = 300 \text{ MW} \times 8760 \text{ h} \times (0.99 – 0.96) \times \text{capacity factor} $$

Assuming a capacity factor of 20% for the coastal site, the gain would be 300×10³ kW × 8760 h × 0.03 × 0.2 = 1.5768×10⁷ kWh, which is an overestimate because availability not equal to capacity factor. The actual measured gain of 5.4431×10⁶ kWh is consistent with the detailed shutdown loss analysis. The significant improvement validates the effectiveness of our “protection–fixation–connection” scheme. It also highlights that addressing cable-related issues is crucial for maximizing the performance of centralized types of solar inverter in coastal environments. Different types of solar inverter may benefit from similar cable protection strategies, but the specific design parameters must be adapted to the cable gauge and tracking system geometry.

4. Conclusion

This study targeted the branch ground fault problem caused by PV1-F 2×4 mm² cables in the horizontal single-axis tracking system of a coastal 300 MW photovoltaic power plant, focusing on improving the availability of centralized types of solar inverter. Through systematic fault mechanism analysis and technological innovation, we achieved the following results:

  1. Root cause identification: We determined that cable abrasion, mechanical stress fatigue, and connector loosening are the three primary causes of PV1-F cable-related branch ground faults, accounting for 90.6% of all such faults. Cable abrasion is strongly linked to the mechanical properties of the XLPE insulation and the sharp edges of tray exits; mechanical stress fatigue results from the lack of dynamic fixation in the tracking system; and connector loosening is exacerbated by salt fog and thermal cycling.
  2. Integrated improvement scheme: We developed a “protection–fixation–connection” solution. The abrasion protection technology uses a EPDM boot with PTFE lining and edge radius polishing, reducing contact stress from 12 MPa to 3 MPa. The dynamic cable fixation employs a three-point method with an adjustable tension device, providing ±3 cm displacement compensation and reducing wear by 5 times. The flexible transition connector features enhanced sealing, longer pin, and locking buckle, elevating plug life to 1000 cycles and maintaining low contact resistance under salt spray.
  3. Field validation: After implementation on 20 test inverter units, the inverter availability increased from 96% to 99%, MTBF extended from 15 days to 92 days, insulation impedance qualification rate rose from 82.0% to 99.5%, and annual generation gain reached 5.4431×10⁶ kWh for the full plant of 144 inverters.

The proposed scheme has been proven effective in a real coastal photovoltaic plant and offers a robust, replicable technical path for improving the operational reliability of types of solar inverter—especially centralized inverters—in harsh environments. Future work could extend the approach to other types of solar inverter such as string inverters or microinverters, adapting the cable protection and fixation methods to their specific cable routing and environmental conditions. Additionally, the use of advanced materials like self-healing polymers and real-time monitoring of cable insulation could further enhance the longevity of the system.