In the context of global energy transition, the large-scale integration of renewable energy sources such as wind power and photovoltaics into the power grid has introduced significant challenges due to their low inertia and high randomness. Traditional thermal power units, constrained by slow ramping rates and response delays, are increasingly unable to meet the stringent requirements for peak regulation and frequency regulation in power systems with a high proportion of renewable energy. With the advancement of battery technology, the highly efficient Battery Energy Storage System (BESS) has emerged as a critical solution to this dilemma. Most existing BESSs are composed of lithium-ion batteries, which offer advantages such as fast response, high energy density, and long cycle life. In peak regulation, the BESS can reduce the peak-valley difference by absorbing and releasing electrical energy; in frequency regulation, it can rapidly compensate for the mismatch between the thermal power unit output and the AGC commands. This thesis focuses on the control strategies for BESS assisting thermal power units in peak regulation and frequency regulation. The research encompasses output characteristics modeling, an improved State of Charge (SOC) estimation algorithm, a peak regulation control strategy based on an improved Beluga Whale Optimization Algorithm (IBWO), and a frequency regulation control strategy based on the Swing Door Trending (SDT) algorithm.

The energy storage battery, as the core component of the BESS, directly determines the efficiency and stability of the entire system. Accurate SOC estimation is the fundamental prerequisite for ensuring the safe and efficient operation of the energy storage battery, particularly in complex working conditions where the ampere-hour integration method suffers from accumulated errors and strong dependence on initial values. To overcome this limitation, I have developed a joint algorithm combining the Forgetting Factor Recursive Least Squares (FFRLS) method with the Extended Kalman Filter (EKF) to estimate the SOC of a lithium-ion energy storage battery under dynamic stress test (DST) conditions. The experimental results demonstrate that the proposed joint algorithm achieves high accuracy, with the estimation error stabilized at approximately 0.8%.
In the realm of BESS-assisted peak regulation, I have formulated a fitness function aimed at reducing the load peak-valley difference while simultaneously minimizing the charging and discharging energy of the BESS. The IBWO algorithm is employed to solve this function, yielding the optimal power allocation between the thermal power unit and the BESS. To prevent overcharging and over-discharging of the energy storage battery, a detailed SOC partition strategy is implemented, determining whether the BESS responds to power regulation commands based on its current SOC region. The effectiveness of this peak regulation control strategy has been verified through winter and summer load curves.
For frequency regulation, I have designed a control strategy based on the SDT algorithm to address the issue of frequent AGC command fluctuations leading to excessive ramping of the thermal power unit. The SDT algorithm compresses and linearly interpolates historical AGC command data, followed by dynamic updating and real-time correction, to generate smooth power regulation commands for the thermal power unit. The BESS then compensates for the difference between the actual thermal power output and the original AGC commands, thereby enhancing frequency regulation performance. SOC partitioning is also applied here to safeguard the energy storage battery. The strategy has been validated using AGC command data from winter and summer periods, alongside historical data from the preceding three days.
Modeling of Thermal Power Unit and BESS Output Characteristics
Due to the influence of steam turbines and speed governors, thermal power units exhibit relatively slow ramping speeds, whether in peak regulation or frequency regulation. The output characteristics of a thermal power unit in these scenarios can be described by considering its ramping rate. The power output at time t is constrained by the maximum ramping rate, denoted as PP,max. The mathematical expression is given by:
$$P_{h}(t) = \begin{cases} P_{h}(t-1) + P_{P,max}, & P_{h,i}(t) > P_{h}(t-1) + P_{P,max} \\ P_{h}(t), & P_{h}(t-1) – P_{P,max} \leq P_{h,i}(t) \leq P_{h}(t-1) + P_{P,max} \\ P_{h}(t-1) – P_{P,max}, & P_{h,i}(t) < P_{h}(t-1) – P_{P,max} \end{cases}$$
where Ph(t) is the actual output of the thermal power unit, Ph,i(t) is the received peak regulation or frequency regulation command, and PP,max is the maximum ramping rate. The operational output of the thermal power unit is also bounded by its minimum and maximum limits: Ph,min ≤ Ph(t) ≤ Ph,max.
Through modular series-parallel configuration, lithium-ion cells can be integrated into megawatt-level BESS. The power constraints of the BESS are expressed as:
$$P_{b}(t) = \begin{cases} P_{b,max}, & P_{b,i}(t) > P_{b,max} \\ P_{b,i}(t), & P_{b,min} \leq P_{b,i}(t) \leq P_{b,max} \\ P_{b,min}, & P_{b,i}(t) < P_{b,min} \end{cases}$$
where Pb(t) is the actual output of the BESS, Pb,i(t) is the received power regulation command, and Pb,max and Pb,min are the maximum charging and discharging powers, respectively, with equal absolute values.
The State of Charge (SOC) represents the remaining capacity of the energy storage battery. In my control strategies, the SOC region determines whether the BESS participates in regulation. The SOC is traditionally estimated using the ampere-hour integration method:
$$SOC(t) = SOC(t_0) + \int_{t_0}^{t} \frac{P_{b}(t)}{C} dt$$
where C is the total capacity of the BESS. While simple and easy to implement, this method suffers from accumulated errors and heavy dependence on initial SOC values, making it unsuitable for complex working conditions. To address these issues, I have developed a joint estimation algorithm based on the second-order RC equivalent circuit model of the lithium-ion energy storage battery.
Improved SOC Estimation Algorithm for Lithium-ion Energy Storage Battery
The second-order RC equivalent circuit model effectively captures the electrochemical polarization and concentration polarization characteristics of the energy storage battery. The circuit consists of an ohmic resistance R0, two RC networks (R1, C1 and R2, C2), and an open-circuit voltage source UOC. Based on Kirchhoff’s laws, the model can be described by:
$$U_{L} = U_{OC} – U_1 – U_2 – I_m R_0$$
where U1 and U2 are the voltages across the two RC networks, Im is the working current, and UL is the terminal voltage. Discretizing the state equations yields the state-space representation with SOC, U1, and U2 as state variables.
The relationship between the open-circuit voltage UOC and SOC is a nonlinear function. Through experimental measurements and polynomial fitting, this relationship is established. A 6th-order polynomial was selected after balancing fitting accuracy and computational cost:
$$U_{OC}(n) = q_1 n^6 + q_2 n^5 + q_3 n^4 + q_4 n^3 + q_5 n^2 + q_6 n + q_7$$
where n is the SOC value and the coefficients q1 through q7 are determined from experimental data. The fitting results show a high coefficient of determination R² = 0.9998, indicating excellent accuracy.
To perform online parameter identification, the equivalent circuit model is transformed into a form suitable for the recursive least squares method. The transfer function is derived, and after applying the bilinear transformation, a difference equation is obtained:
$$y(k) = a_1 y(k-1) + a_2 y(k-2) + a_3 I_m(k) + a_4 I_m(k-1) + a_5 I_m(k-2)$$
where y(k) = UOC(k) – UL(k), and a1 through a5 are the parameters to be identified. The regression vector and parameter matrix are defined accordingly.
The standard recursive least squares method suffers from the “data saturation” problem, where the gain coefficient tends to zero as iterations increase, reducing the influence of new data. The Forgetting Factor Recursive Least Squares (FFRLS) algorithm addresses this by introducing a forgetting factor λ, which is typically set between 0.95 and 1.00. The recursive formulas are:
$$\theta(k) = \theta(k-1) + K(k)\left[y(k) – \varphi(k)^T \theta(k-1)\right]$$
$$K(k) = \frac{P(k-1)\varphi(k)}{\lambda + \varphi(k)^T P(k-1)\varphi(k)}$$
$$P(k) = \frac{1}{\lambda}\left[I – K(k)\varphi(k)^T\right]P(k-1)$$
In my simulations, the forgetting factor λ is set to 0.98, balancing the tracking ability and stability of the estimator. The parameter identification results under DST conditions show that FFRLS can accurately track the variations of the internal resistance and polarization parameters, providing a solid foundation for the subsequent SOC estimation.
The Extended Kalman Filter (EKF) is employed to estimate the SOC of the energy storage battery. The nonlinear state-space model is linearized through Taylor series expansion, neglecting higher-order terms. The EKF recursively performs prediction and update steps, correcting the state estimates through Kalman gain. The system matrices Ak and Bk are the Jacobian matrices of the state transition and measurement functions, respectively. The EKF algorithm consists of initialization, prediction, Kalman gain calculation, and update steps:
Initialization: x₀ = E[x₀], P₀ = E[(x₀ – x̂₀)(x₀ – x̂₀)ᵀ]
Prediction: x̂k|k-1 = h(x̂k-1|k-1, uk), Pk|k-1 = AkPk-1|k-1Akᵀ + Qk
Kalman gain: Kk = Pk|k-1Bkᵀ[BkPk|k-1Bkᵀ + Rk]⁻¹
Update: x̂k|k = x̂k|k-1 + Kk[yk – g(x̂k|k-1, uk)], Pk|k = [I – KkBk]Pk|k-1
The joint algorithm combines FFRLS for online parameter identification with EKF for state estimation. The FFRLS block identifies the model parameters (R₀, R₁, R₂, C₁, C₂) in real-time, which are then used to update the equivalent circuit model. The EKF then estimates the SOC based on this updated model and the measured terminal voltage and current. This synergistic approach ensures high accuracy even under complex working conditions.
Simulation results under DST conditions demonstrate the effectiveness of the joint algorithm. The SOC estimation closely tracks the true value, with the initial deviation rapidly converging to a steady-state error of approximately 0.8%. The terminal voltage estimation also shows high accuracy, with errors maintained within 20 mV. A comparison between different estimation methods is summarized in Table below.
| Method | SOC Estimation Error (%) | Terminal Voltage Error (mV) | Convergence Speed |
|---|---|---|---|
| Ampere-hour Integration | > 5.0 (accumulative) | – | Slow, requires accurate initial SOC |
| EKF (fixed model) | ~ 2.5 | ~ 35 | Moderate |
| FFRLS + EKF (joint) | ~ 0.8 | ~ 18 | Fast |
The proposed joint algorithm efficiently resolves the shortcomings of the ampere-hour integration method, providing accurate and reliable SOC estimation for the energy storage battery in complex operational scenarios. This forms a solid theoretical basis for the control strategies developed in this thesis.
Peak Regulation Control Strategy of BESS Assisting Thermal Power Unit
Improved Beluga Whale Optimization Algorithm
The Beluga Whale Optimization (BWO) algorithm, inspired by the foraging behavior of beluga whales, offers a unique search strategy with good global exploration and local exploitation capabilities. However, it suffers from poor diversity of initial candidate solutions, weak balance between exploration and exploitation, and long optimization times. To overcome these limitations, I have developed an Improved Beluga Whale Optimization Algorithm (IBWO) with three key enhancements:
1. Tent Chaotic Initialization: The Tent chaotic map generates a sequence with randomness, ergodicity, and sensitivity to initial conditions. This sequence replaces the purely random initialization, ensuring that the initial candidate solutions are more uniformly distributed in the solution space. The chaotic sequence is generated as:
$$Z_{i+1} = \begin{cases} \frac{Z_i}{\varphi}, & 0 \leq Z_i \leq \varphi \\ \frac{1-Z_i}{1-\varphi}, & \varphi < Z_i \leq 1 \end{cases}$$
where φ is a chaotic parameter. The initial candidate solutions are then calculated using:
$$X_i = l_b + Z_i (u_b – l_b)$$
where ub and lb are the upper and lower bounds of the search space, respectively.
2. Opposition-Based Learning: To further enhance solution diversity, the Opposition-Based Learning (OBL) technique is applied. For each candidate solution Xi, its opposite solution is calculated as:
$$\overline{X}_i = l_b + u_b – X_i$$
The fitness values of both Xi and its opposite are evaluated, and the better one is selected for the initial population. This approach broadens the search space coverage and increases the probability of finding the global optimum.
3. Improved Balance Factor: The balance factor Bf in the original BWO linearly decreases from 1 to 0.5, resulting in weak adaptive balance between exploration and exploitation. I have introduced a nonlinear balance factor based on the Sigmoid activation function:
$$B_f = \frac{0.5 + \frac{0.5}{1 + e^{-\beta_2 \left(\frac{T}{T_{max}}\right)}}}{2}$$
This nonlinear adjustment allows a more flexible transition between the exploration and exploitation phases, preventing the algorithm from prematurely converging to a local optimum.
To validate the performance of the IBWO, I have conducted comprehensive tests on 12 standard benchmark functions, including 6 unimodal and 6 multimodal functions. The algorithm is compared with several metaheuristic algorithms such as Particle Swarm Optimization (PSO), Differential Evolution (DE), Arithmetic Optimization Algorithm (AOA), Whale Optimization Algorithm (WOA), and the original BWO. The experimental setup includes a population size of 50, a maximum of 500 iterations, and 50 independent runs for each function.
The results are summarized in terms of average value (AV), standard deviation (SD), and operation time (OT). For the unimodal functions (F1 to F6), the IBWO demonstrates superior optimization accuracy and robustness compared to other algorithms. For instance, for function F1, the IBWO achieves an average value of 5.54×10⁻²³¹, significantly outperforming BWO (1.05×10⁻²⁰³) and other algorithms. Similarly, for multimodal functions (F7 to F12), which are used to test the algorithm’s ability to escape local optima, the IBWO consistently finds the global optimum with an AV and SD of zero for most functions, while exhibiting a significantly faster convergence speed than BWO. A representative comparison of the optimization results is shown in the table below.
| Function | Metric | PSO | DE | AOA | WOA | BWO | IBWO |
|---|---|---|---|---|---|---|---|
| F1 | AV | 4.04E-12 | 5.23E-51 | 4.23E-18 | 8.33E-70 | 1.05E-203 | 5.54E-231 |
| F1 | OT/s | 0.119 | 0.311 | 0.065 | 0.322 | 0.318 | 0.229 |
| F8 | AV | 4.53E-01 | 3.33E-01 | 0 | 1.83E-15 | 0 | 0 |
| F8 | OT/s | 0.093 | 0.256 | 0.093 | 0.115 | 0.325 | 0.213 |
These results confirm that the IBWO offers high accuracy, strong robustness, and fast convergence, making it suitable for solving the complex optimization problems encountered in BESS-assisted peak regulation.
Fitness Function for Thermal-Peaking
The objective of the peak regulation control strategy is to minimize the load peak-valley difference while simultaneously minimizing the charging and discharging energy of the BESS. The fitness function is formulated as:
$$f = \frac{f_1}{f_{1,max}} + \frac{f_2}{f_{2,max}}$$
where f1 is the peak-valley difference after the fire-storage joint adjustment, f1,max is the original peak-valley difference of the load curve, f2 is the total daily energy charged/discharged by the BESS, and f2,max is the maximum energy if the BESS operates at its rated power throughout. The detailed expressions are:
$$f_1 = \max \left[ P_{Load}(t) – P_{f,h}(t) – P_{f,b}(t) \right] – \min \left[ P_{Load}(t) – P_{f,h}(t) – P_{f,b}(t) \right]$$
where PLoad(t) is the load power, Pf,h(t) is the thermal power regulation command, and Pf,b(t) is the BESS power command at time t. The original peak-valley difference is:
$$f_{1,max} = \max P_{Load}(t) – \min P_{Load}(t)$$
The BESS charging/discharging energy is:
$$f_2 = \sum_{t=1}^{96} P_{f,b}(t) \Delta t$$
with Δt = 15 minutes and the maximum energy:
$$f_{2,max} = \sum_{t=1}^{96} P_{b,max} \cdot \Delta t$$
Constraints are imposed to ensure the safe operation of the energy storage battery and the thermal power unit:
(1) The BESS power command is limited: |Pf,b(t)| ≤ Pb,max
(2) The SOC variation over a day is constrained: |Σ Pf,b(t)·Δt| ≤ δ·C, where δ = 0.2
(3) The SOC at any time must remain within set limits: SOCmin ≤ SOC(t) ≤ SOCmax
(4) The thermal power unit command is bounded: 130 MW ≤ Pf,h(t) ≤ 330 MW
The fitness function is solved using the IBWO algorithm. The optimization variable is a 192-dimensional vector iX, where the first 96 dimensions represent the thermal power commands and the last 96 dimensions represent the BESS power commands, arranged in chronological order. The maximum iteration number is set to 400, and the population size to 50.
SOC Partition and Output Analysis for Peak Regulation
The output of the thermal power unit is limited by its ramping rate, so the BESS command needs to be adjusted accordingly:
$$\hat{P}_{f,b}(t) = P_{f,b}(t) – P_{h}(t) + P_{f,h}(t)$$
To protect the energy storage battery from overcharging and over-discharging, a detailed SOC partitioning strategy is implemented. The SOC is divided into four zones: the forbidden zone, the high zone, the autonomous regulation zone, and the low zone, as shown conceptually.
(1) Forbidden zone (SOC > SOCmax or SOC < SOCmin): The BESS does not respond to any commands under any circumstances.
(2) High zone (SOChigh < SOC < SOCmax): The BESS only responds to discharge commands to prevent the SOC from entering the forbidden zone during charging.
(3) Autonomous regulation zone (SOClow ≤ SOC ≤ SOChigh): The BESS responds to both charging and discharging commands.
(4) Low zone (SOCmin < SOC < SOClow): The BESS only responds to charging commands.
In my simulations, SOCmax = 0.9, SOCmin = 0.1, SOChigh = 0.65, and SOClow = 0.35. The initial SOC is set to 0.5.
Simulation Validation for Peak Regulation
To validate the proposed peak regulation control strategy, I have used load curve data from a certain thermal power plant during a winter day and a summer day with significant peak-valley variations. The relevant simulation parameters are listed in Table below.
| Parameter | Value |
|---|---|
| Thermal power unit capacity | 330 MW |
| Ramping rate | 1% / min |
| BESS power / capacity | 10 MW / 10 MWh |
| SOC operation upper / lower limit | 0.9 / 0.1 |
| SOC high / low zone | 0.65-0.9 / 0.1-0.35 |
| SOC initial value | 0.5 |
Winter Peak Regulation Simulation: The load curve for a winter day is processed by the IBWO algorithm to obtain the optimal power commands for the thermal power unit and the BESS. The thermal power unit effectively tracks the power regulation commands except in some intervals where the ramping rate limits its response. The BESS responds to its charging/discharging commands, with some deviations due to the maximum power limits and SOC constraints. The SOC curve reveals that the energy storage battery avoids overcharging and over-discharging throughout the day, maintaining its SOC within the predefined zones. The SOC ends at 0.4646, confirming the feasibility of the optimization results.
The comparative analysis of the load curves before and after the peak regulation is shown in Table below. The peak-valley difference is reduced significantly, demonstrating the effectiveness of the control strategy.
| Metric | Before Peak Regulation | After Peak Regulation |
|---|---|---|
| Peak-valley difference (MW) | 293.42 | 246.16 |
| Peak-valley rate | 0.1601 | 0.1498 |
| Reduction in peak-valley difference (MW) | – | 47.26 |
| BESS total energy charged/discharged (MWh) | – | 40.93 |
Summer Peak Regulation Simulation: The proposed strategy is further validated with a summer day characterized by a larger peak-valley difference. The thermal power unit and BESS responses are similar to the winter case. The results are summarized in Table below.
| Metric | Before Peak Regulation | After Peak Regulation |
|---|---|---|
| Peak-valley difference (MW) | 775.13 | 653.19 |
| Peak-valley rate | 0.4120 | 0.4030 |
| Reduction in peak-valley difference (MW) | – | 121.94 |
| BESS total energy charged/discharged (MWh) | – | 42.52 |
| SOC at the end of day | – | 0.5423 |
These results demonstrate that the proposed peak regulation control strategy can effectively reduce the load peak-valley difference in various seasons and load conditions, thereby mitigating the impact on the power grid and ensuring the safe and stable operation of the equipment, while maintaining the sustainable regulation capability of the BESS.
Frequency Regulation Control Strategy of BESS Assisting Thermal Power Unit Tracking AGC Commands
AGC Frequency Regulation Mechanism of Thermal Power Units
In modern power systems, the secondary frequency regulation (AGC) adjusts the power output of generators to maintain the system frequency at its nominal value. When a disturbance occurs, such as a sudden increase in load, the thermal power unit needs to increase its output. However, the response is delayed by the dead zone and limited by the ramping rate. The BESS, with its fast response and precise control capabilities, can effectively compensate for these deficiencies.
Determination of Thermal Power Unit Power Regulation Commands Based on SDT Algorithm
The AGC commands in modern power systems exhibit significant complexity, often fluctuating frequently within short periods. Directly tracking these commands with the thermal power unit leads to excessive ramping frequency, increasing equipment wear and reducing the operational stability of the grid. To address this issue, I propose a method based on the Swing Door Trending (SDT) algorithm to generate smooth power regulation commands for the thermal power unit.
AGC Command Compression and Linear Interpolation: The SDT algorithm is applied to compress historical AGC command data. The algorithm initializes with the first data point and uses a parallelogram with a fixed height (the gate width E) to determine whether subsequent data points can be represented by the previous saved point. If a data point falls outside the parallelogram, the previous point is saved as a feature data point. The gate width E is set to the maximum ramping rate PP,max based on data compression accuracy and computational efficiency. After compression, linear interpolation is performed to obtain a smooth preliminary command curve, denoted as Pf1.
Dynamic Update of Commands: To improve the accuracy of the command, historical AGC data from the previous three days in the same time period are incorporated. The SDT-compressed results from these days are combined, and their corresponding time points are merged to define a set of dynamic update instants. At these instants, a threshold criterion M is used to decide whether to update the command with the actual current-day AGC command. The dynamic update formula is:
$$P_{f2}(t) = \begin{cases} P_{r}(t), & |P_{r}(t) – P_{f1}(t)| > M \\ P_{f1}(t), & |P_{r}(t) – P_{f1}(t)| \leq M \end{cases}$$
where Pr(t) is the actual AGC command and M is the threshold. The accuracy of Pf2 is evaluated for different numbers of historical days, as shown in Table below. The accuracy improves significantly with more days, reaching 94.82% with three days of historical data.
| Number of Previous Days | Dynamic Update Points | Accuracy of Pf2 (%) |
|---|---|---|
| 1 | 101 | 88.44% |
| 2 | 204 | 91.89% |
| 3 | 284 | 94.82% |
Real-Time Correction: Despite the dynamic update, some points may still have a large deviation from the actual AGC command, particularly in cases of abrupt command changes. To further enhance accuracy, a real-time correction is applied. If the difference between the actual AGC command at time t and the previous time step t-1 exceeds the maximum ramping rate PP,max, the command is considered to have changed abruptly, and Pf2(t) is corrected to the actual AGC command Pr(t). The corrected command Pf3(t) is given by:
$$P_{f3}(t) = \begin{cases} P_{r}(t), & |P_{r}(t) – P_{r}(t-1)| > P_{P,max} \\ P_{f2}(t), & |P_{r}(t) – P_{r}(t-1)| \leq P_{P,max} \end{cases}$$
This three-stage process produces a smooth yet accurate power regulation command that reflects the trends of the actual AGC commands while filtering out minor fluctuations.
SOC Partition and Output Analysis for Frequency Regulation
Similar to the peak regulation strategy, the SOC of the energy storage battery is partitioned to ensure safety. However, since the frequency regulation commands are more frequent and random, the high and low zones are set narrower. I set SOChigh = 0.8 and SOClow = 0.2. The response rules are analogous to those in the peak regulation case. The BESS power command is calculated as:
$$P_{r,b}(t) = P_{r}(t) – P_{h}(t)$$
where Ph(t) is the actual thermal power output. The actual BESS output is determined based on the SOC region and the sign of the command:
(1) SOC in forbidden zone, SOC in high zone with Pr,b(t) > 0, or SOC in low zone with Pr,b(t) < 0: Pb(t) = 0
(2) SOC in high zone with Pr,b(t) < 0: respond within limits
(3) SOC in autonomous zone: respond to both charging and discharging commands
(4) SOC in low zone with Pr,b(t) > 0: respond within limits
Simulation Validation for Frequency Regulation
The proposed frequency regulation control strategy is validated using AGC command data from the same thermal power plant. For winter, the period 16:00-17:00 is selected, and for summer, the period 03:00-04:00 with larger fluctuations is analyzed. Historical AGC data from the previous three days are used. The simulation parameters are listed in Table below.
| Parameter | Value |
|---|---|
| Thermal power unit capacity | 330 MW |
| Ramping rate | 2% / min |
| BESS power / capacity | 10 MW / 10 MWh |
| SOC operation upper / lower limit | 0.9 / 0.1 |
| SOC high / low zone | 0.8-0.9 / 0.1-0.2 |
| SOC initial value (winter / summer) | 0.3 / 0.5 |
Winter Frequency Regulation: The thermal power unit tracks the Pf3 command instead of the actual AGC command, resulting in a lower variance in output. The variance is reduced from 37.8695 MW² (direct tracking) to 35.1186 MW² (tracking Pf3), indicating fewer ramping operations. The BESS responds to its commands, with some intervals unresponsive due to SOC limitations. The SOC curve remains within the safe range, avoiding overcharging and over-discharging.
The overall frequency regulation accuracy is evaluated by defining accurate tracking as the difference between the total output (thermal + BESS) and the actual AGC command being within 1 MW. The results are shown in Table below.
| Scenario | Accuracy of Thermal Unit Only (%) | Accuracy with BESS Assistance (%) |
|---|---|---|
| Winter | 83.36% | 97.35% |
| Summer | 78.36% | 95.89% |
Summer Frequency Regulation: The summer AGC commands exhibit larger fluctuations. The thermal power unit variance is reduced from 42.5426 MW² to 38.7648 MW² when tracking Pf3. The BESS effectively compensates for the tracking errors, especially during periods of abrupt command changes. The SOC remains within the safe operating range, and the BESS correctly responds to charging/discharging commands according to its SOC region.
Both winter and summer simulations confirm that the proposed frequency regulation control strategy can effectively reduce the ramping frequency of the thermal power unit while maintaining high tracking accuracy, thereby enhancing the grid frequency stability and reducing equipment wear.
Conclusion and Future Work
This thesis has presented a comprehensive study on the control strategies for BESS assisting thermal power units in peak regulation and frequency regulation. The main contributions and conclusions are summarized as follows:
(1) I have developed a joint SOC estimation algorithm for the lithium-ion energy storage battery, combining FFRLS for online parameter identification and EKF for state estimation. The algorithm achieves high accuracy under dynamic stress test conditions, with an estimation error stable at around 0.8%, overcoming the limitations of the ampere-hour integration method.
(2) I have proposed a peak regulation control strategy based on the improved Beluga Whale Optimization Algorithm. The IBWO, enhanced with Tent chaotic initialization, opposition-based learning, and a nonlinear balance factor, demonstrates superior performance in solving the fitness function. The strategy effectively reduces the load peak-valley difference while preserving the sustainable regulation capability of the BESS, as verified through winter and summer simulations.
(3) I have designed a frequency regulation control strategy based on the SDT algorithm. This strategy generates smooth power regulation commands for the thermal power unit by compressing, interpolating, dynamically updating, and real-time correcting historical AGC data. The BESS compensates for the residual difference, significantly improving the AGC tracking accuracy while reducing the ramping frequency of the thermal power unit.
For future work, several aspects can be further explored. The forgetting factor in the FFRLS algorithm could be replaced with a dynamic forgetting factor to further improve parameter identification accuracy. Moreover, the BESS can be divided into multiple energy storage battery units with different initial SOCs, and a more granular control strategy can be studied to optimize the utilization of each unit. In addition, the economic benefits of the BESS in the auxiliary service market, considering factors such as battery degradation and energy arbitrage, could be incorporated into the optimization framework to provide a more comprehensive solution for practical applications.