Accurately assessing the State of Health (SOH) of energy storage batteries is critical for ensuring the safety, efficiency, and longevity of battery energy storage systems (BESS), which are pivotal components in modern power grids and renewable energy integration. Traditional SOH estimation methods often rely on laboratory data obtained under controlled, full-cycle conditions, which do not reflect the fragmented and variable operational profiles of real-world energy storage batteries in applications like photovoltaic (PV) power stations. This discrepancy leads to significant estimation errors when models are deployed in engineering settings. To address this, our research focuses on developing a practical SOH estimation framework that utilizes readily available operational data fragments from energy storage battery systems. By analyzing actual charging segments and integrating mechanistic insights with data-driven modeling, we aim to enhance the accuracy and field adaptability of SOH monitoring for energy storage batteries.

The operational paradigm of large-scale energy storage battery systems, such as those in PV plants, often involves partial state-of-charge (SOC) cycling and irregular full charges due to grid demands and system management strategies. Consequently, continuous, complete charge-discharge data is seldom available. Instead, data logging typically captures fragmented sequences—short segments of voltage, current, and time at fixed intervals (e.g., 1 minute). Our work demonstrates that even such limited data fragments, if properly selected, contain rich information about the degradation state of an energy storage battery. The core innovation lies in identifying a specific charging voltage region that is both commonly present in operational data and highly sensitive to aging mechanisms, thereby enabling reliable SOH estimation without requiring full-cycle laboratory tests.
To establish a robust methodology, we first conducted a detailed analysis of operational data from a 50 MW/100 MWh PV-plus-storage power station. The energy storage battery system in this station utilizes lithium iron phosphate (LFP) cells with a nominal capacity of 260 Ah. The analysis revealed that during charging cycles aimed at PV energy absorption, the battery cluster often ceased charging when the cluster SOC reached near 100% or when any single cell voltage hit 3.65 V. Examination of multiple charging termination events showed that individual cell voltages at the end of charge were consistently below 3.45 V, and more importantly, all cells exhibited a stable constant-current charging phase at approximately 0.5 C for over 30 minutes before reaching 3.41 V. This finding is crucial because it indicates that a consistent, exploitable data fragment—specifically, the voltage trajectory during a stable current charge within a specific voltage window—is regularly available in the operational history of these energy storage battery units.
Parallel to field data analysis, we performed simulated cycling experiments on 20 Ah LFP energy storage battery samples in a laboratory to generate a controlled dataset with known SOH labels. The simulation mirrored the identified field conditions: cycling within an SOC window of 20% to 100% using a constant charge/discharge current of 0.5 C (10 A), with charging terminated at 3.65 V. Periodic reference capacity tests were conducted to determine the true SOH. The degradation trend was linear, and incremental capacity analysis (ICA) was performed to understand the aging signature. The differential voltage (dV/dQ) curves clearly showed that the most pronounced shift due to aging occurred in a voltage peak (P2) located within the charging region below 3.41 V. This region corresponds to a phase transition in the LFP cathode and is highly sensitive to loss of active lithium and anode active material. Therefore, the voltage change during this specific interval serves as a potent health indicator for the energy storage battery.
Based on this dual analysis—operational feasibility and mechanistic relevance—we selected the charging voltage difference over the 30 minutes preceding the cell voltage reaching 3.41 V as the primary feature for SOH estimation. To account for different data recording granularities, we extracted this feature using three different time intervals between voltage sampling points: 1 minute, 3 minutes, and 5 minutes. This resulted in three distinct feature vectors for each charging cycle. For the 1-minute interval, the feature vector comprises 29 voltage differences (ΔV1, ΔV2, …, ΔV29). For the 3-minute interval, it comprises 9 differences, and for the 5-minute interval, 5 differences. The SOH label for each cycle is calculated from the reference capacity test using the standard definition:
$$SOH = \frac{Q_C}{Q_{new}} \times 100\%$$
where \(Q_C\) is the current maximum available capacity and \(Q_{new}\) is the nominal capacity. For the simulated cycling between 20% and 100% SOC, the measured capacity \(Q_s\) was converted to an equivalent full-cycle capacity \(Q_d\) for SOH calculation using:
$$Q_d = \frac{Q_s}{0.8}$$
Data preprocessing involved normalization of all feature vectors to a [0, 1] range to ensure stable and efficient neural network training:
$$X’ = \frac{X – X_{min}}{X_{max} – X_{min}}$$
where \(X\) is the original feature value, and \(X_{min}\) and \(X_{max}\) are the minimum and maximum values of that feature across the entire dataset, respectively.
The modeling approach employs a hybrid Genetic Algorithm-optimized Backpropagation Neural Network (GA-BP NN). Standard BP neural networks are powerful for nonlinear mapping but are prone to converging to local minima due to random initialization of weights and biases. The Genetic Algorithm introduces a global search capability to optimize the initial weight and threshold matrix of the BP network before the gradient-descent training begins. The GA process involves encoding network parameters into chromosomes, applying selection, crossover, and mutation operations over generations to evolve a population towards an optimal set of initial parameters. This synergy enhances the convergence speed and prediction accuracy of the final model. Our network architecture for the primary model (M-1) consists of an input layer with nodes matching the feature vector length (e.g., 29 for 1-min intervals), three hidden layers with 10 neurons each, and a single output neuron for the predicted SOH value.
The dataset from three 20 Ah energy storage battery cells (over 12,300 cycles in total) was split into training and testing sets in an 8:2 ratio. An additional validation set of 1200 cycles from a separate, identically manufactured cell was used for final accuracy evaluation. The performance of models built on the three different feature sets (1-min, 3-min, and 5-min intervals) was compared using two standard error metrics: Mean Absolute Percentage Error (MAPE) and Root Mean Square Error (RMSE).
$$E_{MAP} = \frac{1}{N} \sum_{n=1}^{N} \left| \frac{Y(n) – S(n)}{S(n)} \right| \times 100\%$$
$$E_{RMS} = \sqrt{ \frac{1}{N} \sum_{n=1}^{N} (Y(n) – S(n))^2 }$$
where \(Y(n)\) is the predicted SOH for sample \(n\), \(S(n)\) is the measured SOH, and \(N\) is the total number of samples.
The results unequivocally demonstrated the superiority of the model using the 1-minute interval voltage difference features. The prediction versus measured SOH plots showed the tightest clustering along the line of perfect agreement for Model M-1. The quantitative error analysis is summarized in the table below:
| Model Name | Feature Parameter (Time Interval) | MAPE (%) | RMSE |
|---|---|---|---|
| M-1 | 1-minute voltage difference | 0.37 | 0.4565 |
| M-2 | 3-minute voltage difference | 0.40 | 0.5095 |
| M-3 | 5-minute voltage difference | 0.44 | 0.5224 |
While all models achieved high accuracy, the gradual increase in error with larger time intervals suggests that finer temporal resolution preserves more degradation-related information from the charging curve of the energy storage battery. The 1-minute interval model effectively captures the subtle shape changes in the voltage profile that correlate with capacity fade.
A significant challenge in deploying data-driven models for energy storage battery management is their lack of generalization across different battery capacities or slight manufacturing variations. To test and improve the generalizability of our best model (M-1), we evaluated it directly on a set of 260 Ah LFP energy storage batteries—the same type used in the PV power station. Without any adjustment, the model applied to these larger cells produced a maximum estimation error of 5.52%, indicating a clear capacity-dependent bias. To rectify this, we employed a transfer learning strategy. Instead of building a new model from scratch—which would require a large amount of labeled data from the 260 Ah cells—we leveraged the pre-trained M-1 model as a foundation. The weights and biases of the first two hidden layers were frozen, as they likely capture universal features related to LFP battery aging from the voltage profile. We then used a small set of 60 charging fragments with corresponding SOH labels from the 260 Ah energy storage batteries to retrain only the final hidden layer and the output layer of the network. This process effectively “calibrates” the model to the new battery size with minimal data. The results were dramatic: the maximum estimation error for the 260 Ah energy storage batteries dropped from 5.52% to 1.89%. This demonstrates the power of transfer learning in adapting fragment-data-based SOH models across similar but non-identical energy storage battery populations, a common scenario in real-world energy storage systems.
The ultimate test of the model’s utility is its application to actual field data where no laboratory SOH labels exist. We implemented the transferred model (based on M-1) to perform batch SOH estimation on one full cluster of 224 series-connected 260 Ah energy storage battery cells in the aforementioned PV power station. Using a single day’s charging data fragment for each cell (the 30-minute voltage sequence before reaching 3.41 V), the model generated SOH estimates for all 224 cells. The results, presented in the table below, show a tight distribution of SOH values around 95%, which is consistent with the expected health of cells in an operational system. This successful bulk estimation proves the model’s strong engineering adaptability and its potential for integration into battery management systems (BMS) for continuous, non-invasive health monitoring of energy storage battery banks.
| Battery Cell Index Range | Estimated SOH Range (%) | Mean Estimated SOH (%) | Standard Deviation |
|---|---|---|---|
| 1 – 224 | 94.8 – 95.5 | 95.15 | 0.18 |
The methodology presented here underscores several important principles for the condition monitoring of energy storage batteries. First, the choice of feature is paramount; it must be derivable from available operational data and intrinsically linked to the fundamental aging physics of the energy storage battery. The charging voltage curve fragment below 3.41 V for LFP cells fulfills both criteria. Second, the hybrid GA-BP neural network provides a robust framework for learning the complex, nonlinear relationship between this fragmentary input and the scalar SOH output. Third, transfer learning is an essential tool for bridging the “reality gap” between laboratory models and fielded energy storage battery systems, enabling accurate estimation with minimal additional calibration data.
Looking forward, this fragment-based approach can be extended to other lithium-ion chemistries used in energy storage batteries, such as lithium nickel manganese cobalt oxide (NMC), by identifying their own characteristic voltage regions sensitive to degradation. Furthermore, the model could be adapted to estimate other states, such as State of Power (SOP) or to predict Remaining Useful Life (RUL), by incorporating temporal sequences of the extracted features. The integration of this estimation routine into cloud-based analytics platforms for energy storage battery fleets could enable predictive maintenance and optimize system-level operation, ultimately enhancing the economic value and safety of grid-scale energy storage resources.
In conclusion, we have developed and validated a practical, high-accuracy method for estimating the State of Health of energy storage batteries using fragmented charging data commonly available in their operational environment. By focusing on a mechanistically significant voltage window and employing an optimized neural network with transfer learning capabilities, the method overcomes key limitations of traditional models. It provides a viable path for real-world, large-scale health assessment of energy storage battery systems, contributing to more reliable and efficient renewable energy integration and power grid stabilization. The continued evolution of such data-driven techniques will be instrumental in managing the lifespan and performance of the growing global fleet of energy storage batteries.