In modern power systems, the integration of renewable energy sources heavily relies on power electronic interfaces, with the grid-tied inverter playing a pivotal role. As a critical component, the grid-tied inverter converts DC power from sources like solar panels or batteries into AC power synchronized with the utility grid. The performance of this grid-tied inverter directly impacts power quality, system stability, and overall efficiency. Traditional control strategies, such as proportional-integral (PI) control, hysteresis control, and proportional-resonant (PR) control, have been widely adopted. However, these methods often suffer from limitations like sensitivity to parameter variations, variable switching frequencies, and compromised dynamic response. For instance, PI control can lead to overshoot and slow transient recovery, while hysteresis control introduces significant harmonic distortion due to unfixed switching patterns. These issues underscore the need for advanced control techniques that enhance robustness and adaptability in grid-tied inverter applications.
Model predictive control (MPC) has emerged as a promising alternative due to its intuitive formulation and fast dynamic response. By leveraging a system model to predict future behavior and optimizing control actions accordingly, MPC can effectively manage power flow in grid-tied inverters. However, conventional MPC methods depend heavily on accurate mathematical models of the grid-tied inverter, including parameters like inductance, resistance, and capacitance. In practice, these parameters are subject to uncertainties caused by temperature fluctuations, aging, and manufacturing tolerances. Such mismatches degrade control performance, leading to increased current distortion and reduced power quality. To address this, model-free predictive control (MFPC) approaches have been developed, which minimize reliance on precise models. Among these, the ultra-local model technique replaces detailed system dynamics with a simplified representation, focusing on input-output relationships. Yet, challenges persist in handling unknown disturbances, especially under low sampling frequencies where prediction inaccuracies accumulate.
In this article, I propose a novel model-free predictive power control (MFPPC) strategy for three-phase grid-tied inverters, incorporating a compensation function observer (CFO) to estimate and counteract disturbances. The core idea is to enhance the robustness of the grid-tied inverter against parameter variations and external perturbations. First, I construct an ultra-local model for the power dynamics of the grid-tied inverter, reducing dependency on exact physical parameters. Second, I design a CFO that improves upon traditional linear extended state observers (LESOs) by integrating a compensation function, which refines disturbance estimation without amplifying noise. Finally, I formulate a deadbeat cost function to achieve precise power tracking. Experimental results validate that the proposed method outperforms existing approaches in both steady-state and dynamic scenarios. Throughout this discussion, I will emphasize the application to grid-tied inverters, highlighting how each component contributes to reliable operation in renewable energy systems.

The mathematical modeling of a three-phase grid-tied inverter forms the foundation for control design. Consider a standard two-level voltage source inverter connected to the grid through an L filter, where the grid-tied inverter output voltages interact with grid voltages and currents. In the stationary $\alpha\beta$ reference frame, the dynamics can be expressed as:
$$ \begin{aligned}
V_{\alpha} &= R i_{\alpha} + L \frac{di_{\alpha}}{dt} + v_{\alpha} \\
V_{\beta} &= R i_{\beta} + L \frac{di_{\beta}}{dt} + v_{\beta}
\end{aligned} $$
Here, $V_{\alpha}$ and $V_{\beta}$ are the inverter output voltages, $i_{\alpha}$ and $i_{\beta}$ are the grid currents, $v_{\alpha}$ and $v_{\beta}$ are the grid voltages, $L$ is the filter inductance, and $R$ is the equivalent series resistance. The grid voltages evolve with angular frequency $\omega_s$ as:
$$ \frac{dv_{\alpha}}{dt} = -\omega_s v_{\beta}, \quad \frac{dv_{\beta}}{dt} = \omega_s v_{\alpha} $$
Using instantaneous power theory, the active power $P_{ac}$ and reactive power $Q_{ac}$ for the grid-tied inverter are given by:
$$ P_{ac} = \frac{3}{2}(v_{\alpha} i_{\alpha} + v_{\beta} i_{\beta}), \quad Q_{ac} = \frac{3}{2}(v_{\beta} i_{\alpha} – v_{\alpha} i_{\beta}) $$
Differentiating these expressions and substituting the current dynamics yields the power model:
$$ \begin{aligned}
\frac{dP_{ac}}{dt} &= \frac{3}{2L}(V_{\alpha} v_{\alpha} + V_{\beta} v_{\beta} – v_{\alpha}^2 – v_{\beta}^2) – \omega_s Q_{ac} – \frac{R}{L} P_{ac} \\
\frac{dQ_{ac}}{dt} &= \frac{3}{2L}(V_{\alpha} v_{\beta} – V_{\beta} v_{\alpha}) + \omega_s P_{ac} – \frac{R}{L} Q_{ac}
\end{aligned} $$
This model is essential for model predictive control but requires accurate knowledge of $L$ and $R$. In real-world grid-tied inverter applications, these parameters vary, necessitating a model-free approach.
To transition to model-free predictive control, I employ an ultra-local model that approximates the system behavior without detailed parameters. For a first-order system, the ultra-local model is:
$$ \dot{y} = \alpha u + f $$
where $y$ is the output (e.g., power), $\alpha$ is a tuning gain, $u$ is the input, and $f$ encapsulates all unknown dynamics and disturbances. For the grid-tied inverter, I apply this to both active and reactive power loops:
$$ \begin{aligned}
\frac{dP_{ac}}{dt} &= b_1 V_p + f_p \\
\frac{dQ_{ac}}{dt} &= b_2 V_q + f_q
\end{aligned} $$
Here, $V_p$ and $V_q$ are control inputs derived from voltage components, $b_1$ and $b_2$ are input gains, and $f_p$, $f_q$ are lumped disturbances. The disturbances include terms like $-\omega_s Q_{ac} – \frac{R}{L} P_{ac}$ and $\omega_s P_{ac} – \frac{R}{L} Q_{ac}$, which are treated as unknowns. The input gains can be set as $b_1 = b_2 = 3/(2L_{\text{nom}})$, where $L_{\text{nom}}$ is a nominal inductance value for the grid-tied inverter. Discretizing using forward Euler method with sampling time $T_s$:
$$ \begin{aligned}
P_{ac}(k+1) &= P_{ac}(k) + T_s [b_1 V_p(k) + f_p(k)] \\
Q_{ac}(k+1) &= Q_{ac}(k) + T_s [b_2 V_q(k) + f_q(k)]
\end{aligned} $$
A deadbeat cost function is then designed to achieve accurate tracking:
$$ g = [P_{ac}^* – P_{ac}(k+1)]^2 + [Q_{ac}^* – Q_{ac}(k+1)]^2 $$
Minimizing $g$ yields the optimal control inputs:
$$ V_p^* = \frac{P_{ac}^* – P_{ac}(k)}{b_1 T_s} – \frac{f_p(k)}{b_1}, \quad V_q^* = \frac{Q_{ac}^* – Q_{ac}(k)}{b_2 T_s} – \frac{f_q(k)}{b_2} $$
However, accurate estimation of $f_p$ and $f_q$ is critical for the grid-tied inverter’s performance. Traditional observers like LESO can estimate disturbances but may suffer from noise amplification when bandwidth is increased. To overcome this, I propose a compensation function observer (CFO) that enhances estimation accuracy without compromising stability.
The CFO extends the LESO structure by adding an integral compensation term. Consider a state-space representation of the ultra-local model for the grid-tied inverter:
$$ \begin{aligned}
\dot{x} &= A x + B u + E f \\
y &= C x
\end{aligned} $$
with $x = [x_1, x_2]^T$, where $x_1 = y$ (power) and $x_2 = f$ (disturbance). The matrices are:
$$ A = \begin{bmatrix} 0 & 1 \\ 0 & 0 \end{bmatrix}, \quad B = \begin{bmatrix} \alpha \\ 0 \end{bmatrix}, \quad C = \begin{bmatrix} 1 & 0 \end{bmatrix}, \quad E = \begin{bmatrix} 0 \\ 1 \end{bmatrix} $$
A conventional LESO estimates states as:
$$ \begin{aligned}
\dot{\hat{x}} &= A \hat{x} + B u + H (y – \hat{y}) \\
\hat{y} &= C \hat{x}
\end{aligned} $$
where $H = [l_1, l_2]^T$ is the gain vector. The gains are typically set as $l_1 = 2\omega$, $l_2 = \omega^2$ for bandwidth $\omega$. While effective, this observer has limitations in reducing estimation residuals. The CFO modifies this by introducing a compensation function $\hat{f}_c$:
$$ \begin{aligned}
\dot{\hat{x}} &= A \hat{x} + B u + H (y – \hat{y}) + E \hat{f}_c \\
\hat{y} &= C \hat{x} \\
\dot{\hat{f}}_c &= \lambda H (y – \hat{y}) + E \hat{f}_c
\end{aligned} $$
Here, $\hat{f}_c$ is an additional state that compensates for estimation errors. By incorporating a first-order filter with factor $\lambda$, the CFO achieves smoother disturbance rejection. The discrete-time implementation for the grid-tied inverter is:
$$ \begin{aligned}
\hat{x}_1(k+1) &= \hat{x}_1(k) + T_s [\hat{x}_2(k) + l_1 e(k) + \alpha u(k)] \\
\hat{x}_2(k+1) &= \hat{x}_2(k) + T_s [l_2 e(k) + \hat{x}_3(k)] \\
\hat{x}_3(k+1) &= \hat{x}_3(k) + \lambda l_2 T_s e(k)
\end{aligned} $$
with $e(k) = x_1(k) – \hat{x}_1(k)$. The parameters are chosen based on stability analysis: $l_1 = 9\omega$, $l_2 = 24\omega^2$, $\lambda = 2\omega/3$, ensuring all poles are in the left half-plane. This structure improves the grid-tied inverter’s resilience to parameter shifts, as the compensation function adapts to residual errors.
To validate the proposed CFO-based MFPPC, I conducted experiments on a three-phase grid-tied inverter platform. The system parameters are summarized in Table 1, which highlights key specifications for the grid-tied inverter setup.
| Parameter | Symbol | Value |
|---|---|---|
| DC Input Voltage | $V_{dc}$ | 200 V |
| Grid Voltage (phase) | $V_a$ | 50 V |
| Filter Inductance | $L$ | 10 mH |
| Series Resistance | $R$ | 0.3 Ω |
| Sampling Frequency | $f_s$ | 10 kHz |
| Grid Frequency | $f_g$ | 50 Hz |
The control algorithms were implemented on a DSP28377D processor, comparing the proposed CFO-MFPPC against a baseline LESO-based MFPPC for the grid-tied inverter. Steady-state tests were performed with active power set at 800 W and reactive power at 0 VAR. The current waveforms and harmonic analysis demonstrate the superiority of the CFO approach. Table 2 compares key performance metrics for the grid-tied inverter under steady-state conditions.
| Metric | LESO-MFPPC | CFO-MFPPC | Improvement |
|---|---|---|---|
| Current THD | 4.61% | 4.07% | 0.54% reduction |
| Active Power Ripple | 15 W | 10 W | 33% reduction |
| Reactive Power Error | 5 VAR | 2 VAR | 60% reduction |
The total harmonic distortion (THD) is a critical indicator for grid-tied inverter power quality. The CFO-MFPPC achieves lower THD, complying with grid standards (e.g., below 5%). This enhancement stems from more accurate disturbance estimation, which reduces current distortions in the grid-tied inverter output.
Dynamic performance was evaluated through step changes in active power reference from 600 W to 1000 W. The response times and overshoot are quantified in Table 3, showcasing the grid-tied inverter’s behavior under transient conditions.
| Algorithm | Settling Time (ms) | Overshoot (A) | Power Recovery (ms) |
|---|---|---|---|
| LESO-MFPPC | 7.5 | 1.2 | 8.0 |
| CFO-MFPPC | 2.6 | 0.5 | 3.0 |
The CFO-MFPPC significantly reduces settling time by over 65%, indicating faster convergence for the grid-tied inverter. This is vital for applications requiring rapid power adjustments, such as in renewable energy systems where grid-tied inverters must respond to fluctuating generation.
Parameter robustness tests involved varying the filter inductance $L$ from 2.5 mH to 25 mH, simulating aging or temperature effects in the grid-tied inverter. The results, summarized in Table 4, highlight the resilience of the proposed method.
| Inductance Change | LESO-MFPPC Recovery Time (ms) | CFO-MFPPC Recovery Time (ms) | Current Overshoot (A) |
|---|---|---|---|
| 2.5 mH → 10 mH | 160.4 | 98.3 | 4.2 vs 1.9 |
| 10 mH → 25 mH | 92.4 | 38.4 | 1.2 vs 0.7 |
The CFO-MFPPC exhibits shorter recovery times and lower overshoot, confirming its enhanced adaptability for grid-tied inverters facing parameter uncertainties. This robustness is attributed to the compensation function, which continuously refines disturbance estimates, ensuring stable operation of the grid-tied inverter even under non-ideal conditions.
To further illustrate the control structure, I present the overall block diagram equations for the grid-tied inverter system. The power references $P_{ac}^*$ and $Q_{ac}^*$ are generated based on grid requirements. The CFO estimates disturbances $\hat{f}_p$ and $\hat{f}_q$ using the ultra-local model:
$$ \begin{aligned}
\hat{f}_p(k) &= \hat{x}_{2,p}(k) \quad \text{(from active power CFO)} \\
\hat{f}_q(k) &= \hat{x}_{2,q}(k) \quad \text{(from reactive power CFO)}
\end{aligned} $$
The optimal voltages are computed as:
$$ \begin{aligned}
V_{\alpha}^* &= \frac{v_{\alpha}(k) V_p^* + v_{\beta}(k) V_q^*}{v_{\alpha}^2(k) + v_{\beta}^2(k)} \\
V_{\beta}^* &= \frac{v_{\beta}(k) V_p^* – v_{\alpha}(k) V_q^*}{v_{\alpha}^2(k) + v_{\beta}^2(k)}
\end{aligned} $$
These are then fed to a space vector pulse-width modulation (SVPWM) module to generate switching signals for the grid-tied inverter. The discrete-time CFO update laws ensure real-time feasibility for the grid-tied inverter implementation.
The stability of the CFO can be analyzed through Lyapunov methods. Defining estimation errors $e_1 = x_1 – \hat{x}_1$, $e_2 = x_2 – \hat{x}_2$, and $e_3 = f – \hat{f}_c$, the error dynamics are:
$$ \begin{aligned}
\dot{e}_1 &= e_2 – l_1 e_1 \\
\dot{e}_2 &= e_3 – l_2 e_1 \\
\dot{e}_3 &= \dot{f} – \lambda l_2 e_1
\end{aligned} $$
Assuming bounded disturbance derivative $\dot{f}$, i.e., $|\dot{f}| \leq \delta$, a Lyapunov function $V = \frac{1}{2}(e_1^2 + e_2^2 + e_3^2)$ yields:
$$ \dot{V} = e_1 \dot{e}_1 + e_2 \dot{e}_2 + e_3 \dot{e}_3 \leq -l_1 e_1^2 – l_2 e_2^2 + \delta |e_3| $$
With proper choice of $l_1$, $l_2$, and $\lambda$, the errors converge exponentially, ensuring stability for the grid-tied inverter control system. This theoretical guarantee underpins the practical efficacy of the CFO in grid-tied inverter applications.
In addition to experimental results, I performed simulation studies to explore corner cases. For instance, under grid voltage sags or harmonics, the grid-tied inverter must maintain stable power injection. The CFO-MFPPC demonstrates superior rejection of grid disturbances compared to traditional methods. A key formula for assessing performance is the error in power tracking:
$$ \epsilon_P = \frac{1}{N} \sum_{k=1}^{N} |P_{ac}^* – P_{ac}(k)| $$
where $N$ is the number of samples. For the grid-tied inverter with CFO-MFPPC, $\epsilon_P$ is reduced by approximately 40% relative to LESO-MFPPC in scenarios with 10% grid voltage unbalance. This highlights the method’s suitability for real-world grid-tied inverter deployments where grid conditions are often imperfect.
Another aspect is computational burden. The CFO adds minimal complexity to the grid-tied inverter control algorithm. The additional state $\hat{x}_3$ requires only a few arithmetic operations per cycle. Table 5 compares execution times for different control strategies on the DSP platform, emphasizing practicality for grid-tied inverters.
| Algorithm | Execution Time (µs) | Memory Usage (KB) | Suitability for Real-Time |
|---|---|---|---|
| PI Control | 5.2 | 2.1 | High |
| LESO-MFPPC | 12.8 | 4.5 | Medium |
| CFO-MFPPC | 14.3 | 5.0 | High |
The CFO-MFPPC incurs a modest increase in execution time (about 12% over LESO-MFPPC), which is acceptable given its performance benefits for the grid-tied inverter. This makes it feasible for high-switching-frequency grid-tied inverters where control cycles are short.
Future work could explore adaptive tuning of the CFO parameters (e.g., $\omega$ and $\lambda$) based on operating conditions of the grid-tied inverter. For example, in a grid-tied inverter system with varying grid impedance, online adaptation could further enhance robustness. Additionally, extending the CFO to multi-objective optimization for grid-tied inverters, such as minimizing switching losses while maintaining power quality, presents an interesting direction.
In conclusion, the proposed CFO-based model-free predictive power control offers a robust solution for three-phase grid-tied inverters. By leveraging an ultra-local model and a novel compensation function observer, the method reduces dependency on precise parameters and improves disturbance rejection. Experimental results confirm significant improvements in steady-state current quality, dynamic response, and parameter robustness for the grid-tied inverter. This approach aligns with the growing demand for reliable and efficient grid-tied inverters in renewable energy integration, contributing to smarter and more resilient power systems.