Fault Characteristic Analysis of Solar Inverters Considering Negative Sequence Control Strategy

With the increasing integration of solar inverters into power systems, understanding their fault characteristics under asymmetrical conditions becomes critical. This paper analyzes steady-state short-circuit current behavior and equivalent negative sequence impedance characteristics of solar inverters under different negative sequence control strategies.

Steady-State Short-Circuit Current Calculation

The output current of solar inverters during asymmetrical faults can be expressed as:

$$i_a = |\boldsymbol{i}^+| \cos(\omega_1 t + \phi^+) + |\boldsymbol{i}^-| \cos(\omega_1 t – \phi^-)$$
$$i_b = |\boldsymbol{i}^+| \cos(\omega_1 t – 120^\circ + \phi^+) + |\boldsymbol{i}^-| \cos(\omega_1 t + 120^\circ – \phi^-)$$
$$i_c = |\boldsymbol{i}^+| \cos(\omega_1 t + 120^\circ + \phi^+) + |\boldsymbol{i}^-| \cos(\omega_1 t – 120^\circ – \phi^-)$$

where $|\boldsymbol{i}^+|$ and $|\boldsymbol{i}^-|$ represent positive and negative sequence current magnitudes, respectively.

Negative Sequence Control Strategies

Three primary control objectives for solar inverters under unbalanced conditions:

Control Objective Mathematical Representation
Suppress Negative Sequence Current $\boldsymbol{i}^- = 0$
Eliminate Reactive Power Oscillation $Q_{c2} = Q_{s2} = 0$
Eliminate Active Power Oscillation $P_{c2} = P_{s2} = 0$

Fault Current Characteristics

The phase relationship between sequence components varies with control strategies:

$$ \phi^+ + \phi^- = \arg[\rho(\boldsymbol{e}^-)] $$

where $\rho$ takes values 0, 1, or -1 depending on the control objective.

Current Magnitude Characteristics Under Different Faults
Control Objective Fault Type
Single-Phase Ground Phase-Phase Fault
Objective I $|i_{fault}| = |\boldsymbol{i}^+|$ $|i_{fault}| = |\boldsymbol{i}^+|$
Objective II $|i_{fault}| = \big||\boldsymbol{i}^+| – |\boldsymbol{i}^-|\big|$ $|i_{fault}| = \sqrt{|\boldsymbol{i}^+|^2 + |\boldsymbol{i}^-|^2 – |\boldsymbol{i}^+||\boldsymbol{i}^-|}$
Objective III $|i_{fault}| = |\boldsymbol{i}^+| + |\boldsymbol{i}^-|$ $|i_{fault}| = \sqrt{|\boldsymbol{i}^+|^2 + |\boldsymbol{i}^-|^2 + |\boldsymbol{i}^+||\boldsymbol{i}^-|}$

Equivalent Negative Sequence Impedance

The equivalent negative sequence impedance of solar inverters is calculated as:

$$ Z^- = -\frac{\boldsymbol{e}^+}{\rho(\boldsymbol{i}^+)} $$

where $\rho$ determines the impedance angle characteristics:

Control Objective Impedance Angle Range
Objective I Infinite impedance
Objective II $-90^\circ$ to $-180^\circ$
Objective III $0^\circ$ to $90^\circ$

Simulation Verification

A 1MW solar inverter model was simulated in PSCAD/EMTDC to validate theoretical analysis:

$$ \text{Grid Parameters: } Z_{pos} = 0.19 + j2.68\Omega, \ Z_{zero} = 1.78 + j8.6\Omega $$

Key observations from phase-ground fault simulations:

  • Objective I produces symmetrical currents with zero negative sequence components
  • Objective II minimizes fault phase current magnitude
  • Objective III maximizes fault phase current magnitude

Practical Implications

The distinct fault characteristics of solar inverters under different negative sequence control strategies require:

  1. Adaptive protection setting calculations
  2. Enhanced fault detection algorithms
  3. Control strategy-aware grid planning

$$ \text{Current Limitation: } i_{max} = 1.2I_N \text{ (during voltage dips)} $$

Modern solar inverters demonstrate flexible fault response characteristics that differ fundamentally from synchronous generators, requiring new approaches for power system protection and stability analysis.

Scroll to Top