In my research on grid-connected photovoltaic systems, I have focused extensively on understanding how solar inverters respond to different types of power grid disturbances. The growing penetration of large-scale photovoltaic power plants into modern power systems demands a thorough comprehension of inverter behavior during grid faults. My work addresses this critical need by examining both symmetrical and asymmetrical fault scenarios, providing theoretical analysis supported by electromagnetic transient simulations.
As solar energy becomes an increasingly significant component of the global energy mix, the behavior of grid-connected solar inverters during fault conditions has attracted considerable attention. Many countries have already established or are in the process of developing grid connection codes specifically for photovoltaic power stations, many of which mandate low voltage ride-through capability. In my analysis, I have observed that unlike wind turbine systems which possess rotational inertia, solar photovoltaic systems lack this mechanical characteristic. The critical constraint for solar inverters during grid faults is not the DC-link overvoltage, but rather the magnitude of output current on the AC side. This fundamental difference shapes the entire approach to analyzing and designing low voltage ride-through strategies for solar inverters.

System Configuration and Control Architecture
In my study, I have focused on the single-stage topology for high-power photovoltaic inverters, which is widely adopted in domestic applications due to its structural simplicity, cost-effectiveness, and minimal power losses. Table 1 summarizes the main circuit parameters of the grid-connected solar inverter system I simulated in my research.
| Parameter | Value |
|---|---|
| Rated Power (kW) | 500 |
| Rated Frequency (Hz) | 50 |
| DC-side Capacitance (μF) | 18,000 |
| AC-side Filter Inductance (mH) | 0.17 |
| AC-side Filter Capacitance (μF) | 200 |
| Transformer Turns Ratio (Dyn1) | 270/400 |
The control strategy I employed for the grid-connected solar inverter is based on grid voltage oriented vector control. This conventional scheme consists of an outer DC voltage loop that performs maximum power point tracking, and an inner current loop that regulates the active and reactive current components. The outer MPPT control generates the DC voltage reference Vdc,ref, which is compared with the actual DC voltage Vdc. The error signal passes through a PI controller to produce the d-axis current reference id,ref. Similarly, the q-axis current reference iq,ref can be adjusted to control reactive power output.
During voltage sags, I have found that the output current of solar inverters is predominantly the active component id. Therefore, preventing overcurrent through the inverter primarily involves limiting the active current reference. In my analysis, I set the reactive current reference iq,ref to zero and restrict id,ref between id,min and id,max, where:
$$i_{d,min} = 0$$
$$i_{d,max} = 1.1$$
One important distinction I noted in solar inverters compared to general-purpose inverters is that the DC-side voltage continuously varies according to the MPPT algorithm’s output. This characteristic requires special consideration in PWM generation. If SPWM modulation is employed, the calculated vd and vq must be normalized by dividing by Vdc/2 before generating trigger pulses. For SVPWM, since the space vector duration calculation already includes division by Vdc/√3, no additional processing of vd and vq is necessary.
Mathematical Modeling under Symmetrical Faults
In my analysis of symmetrical grid faults, I began with the normal operating condition where the grid phase voltage RMS value is denoted as E. The three-phase voltage expressions can be written as:
$$e_a = \sqrt{2}E\cos(\omega_1 t)$$
$$e_b = \sqrt{2}E\cos(\omega_1 t – 2\pi/3)$$
$$e_c = \sqrt{2}E\cos(\omega_1 t + 2\pi/3)$$
After transformation to the synchronous rotating reference frame, I obtained:
$$e_d = \sqrt{2}E$$
$$e_q = 0$$
Under this condition, according to instantaneous reactive power theory, the output active power p of the solar inverter is:
$$p = \frac{3}{2}e_d i_d$$
When a symmetrical grid fault occurs, the grid phase voltage RMS value drops to Ef. Since the fault is three-phase symmetrical, the voltage drop is identical across all phases. The post-fault voltage expressions become:
$$e_{fa} = \sqrt{2}E_f\cos(\omega_1 t + \psi)$$
$$e_{fb} = \sqrt{2}E_f\cos(\omega_1 t + \psi – 2\pi/3)$$
$$e_{fc} = \sqrt{2}E_f\cos(\omega_1 t + \psi + 2\pi/3)$$
After transformation to the synchronous reference frame:
$$e_{fd} = \sqrt{2}E_f$$
$$e_{fq} = 0$$
I determined that the maximum output active power limit pf,max of the solar inverter under symmetrical fault conditions is:
$$p_{f,max} = 1.5 e_{fd} i_{d,max}$$
Through my analysis, I identified two distinct operating scenarios depending on the solar irradiance level. Under high irradiance conditions, if the fault causes p > pf,max, the MPPT control ceases operation, the DC bus voltage Vdc rises rapidly, and id increases to its maximum limit id,max. This allows the system to reach a new operating point where p′ = pf,max, and after fault clearance, the system returns to its original operating state. Under low irradiance conditions, if p < pf,max, the DC bus voltage remains unchanged, id increases rapidly without violating limits, and the operating point remains unchanged.
Power Analysis under Asymmetrical Faults
My analysis of asymmetrical faults required the application of symmetrical component theory. For a three-wire photovoltaic system, there is no zero-sequence path, so the three-phase voltages and currents decompose into positive-sequence and negative-sequence components. I developed vector diagrams illustrating the relationships between voltage and current vectors in both positive and negative synchronous rotating frames.
In these diagrams, the positive-sequence grid voltage vector components are e+d and e+q, while the negative-sequence components are e–d and e–q. Similarly, the current components are i+d, i+q for positive sequence and i–d, i–q for negative sequence. The angle φ between the negative-sequence d-axis and positive-sequence d-axis varies at twice the fundamental frequency.
When three-phase voltages are unbalanced, the output complex power S of the solar inverter is:
$$S = p(t) + jq(t)$$
Using the projection method based on instantaneous reactive power theory, I calculated the active power output in each axis. The positive-sequence d-axis active power is:
$$p_d^+ = 1.5(e_d^+ i_d^+ + e_d^+ i_d^- \cos\varphi + e_d^+ i_q^- \sin\varphi)$$
The positive-sequence q-axis active power:
$$p_q^+ = 1.5(e_q^+ i_q^+ – e_q^+ i_d^- \sin\varphi + e_d^+ i_q^- \cos\varphi)$$
The negative-sequence d-axis active power:
$$p_d^- = 1.5(e_d^- i_d^- + e_d^- i_d^+ \cos\varphi – e_d^- i_q^+ \sin\varphi)$$
The negative-sequence q-axis active power:
$$p_q^- = 1.5(e_q^- i_q^- + e_q^- i_d^+ \sin\varphi + e_q^- i_q^+ \cos\varphi)$$
Therefore, the total active power output of the solar inverter becomes:
$$p(t) = p_d^+ + p_q^+ + p_d^- + p_q^- = p_0 + p_{c2}\cos\varphi + p_{s2}\sin\varphi$$
where p0 represents the average active power (DC quantity), while pc2 and ps2 represent the amplitudes of the cosine and sine terms of the power ripple at twice the fundamental frequency. I derived the following component equations:
$$p_0 = 1.5(e_d^+ i_d^+ + e_q^+ i_q^+ + e_d^- i_d^- + e_q^- i_q^-)$$
$$p_{c2} = 1.5(e_d^+ i_d^- + e_q^+ i_q^- + e_d^- i_d^+ + e_q^- i_q^+)$$
$$p_{s2} = 1.5(e_d^+ i_q^- – e_q^+ i_d^- – e_d^- i_q^+ + e_q^- i_d^+)$$
Similarly, I derived the reactive power components:
$$q_0 = 1.5(e_q^+ i_d^+ – e_d^+ i_q^+ + e_q^- i_d^- – e_d^- i_q^-)$$
$$q_{c2} = 1.5(e_q^+ i_d^- – e_d^+ i_q^- + e_q^- i_d^+ – e_d^- i_q^+)$$
$$q_{s2} = 1.5(e_d^+ i_q^- + e_q^+ i_d^- – e_d^- i_q^+ – e_q^- i_d^+)$$
This mathematical framework clearly demonstrates that under asymmetrical fault conditions, the power output of solar inverters contains oscillatory components at twice the fundamental frequency, which has profound implications for their dynamic behavior.
Impact of Negative-Sequence Currents
In my analysis, I neglected inverter losses to establish the power balance relationship. The DC-side power of the solar inverter equals the AC-side active power, giving:
$$V_{dc}I_{dc} = p_0 + p_{c2}\cos\varphi + p_{s2}\sin\varphi$$
This equation reveals that the DC-side power contains a ripple component at twice the fundamental frequency. Since the DC side of the solar inverter consists of the parallel combination of the photovoltaic array and the DC bus capacitor, neither acting as an ideal voltage source nor an ideal current source, both the DC bus voltage and current contain second-harmonic ripple. The more pronounced the constant voltage source characteristic of the photovoltaic array, the larger the second-harmonic component in the current. Conversely, the more evident the constant current source characteristic, the more significant the voltage ripple. For the voltage-source inverter, the DC bus voltage ripple has a more substantial impact.
When an asymmetrical grid fault occurs, the grid voltage simultaneously contains both positive-sequence and negative-sequence components. Under the conventional control strategy I analyzed, the solar inverter output voltage consists of positive-sequence components. The interaction between the grid voltage positive-sequence components and the inverter output generates positive-sequence currents, while the negative-sequence voltage components act on the limited R, L, and C elements, producing substantial negative-sequence currents. I found that the conventional control strategy only provides satisfactory regulation of positive-sequence currents; it cannot effectively control negative-sequence currents. When positive and negative sequence currents superimpose, one or two phases of the three-phase output current of the solar inverter may exceed the inverter’s tolerance, potentially triggering overcurrent protection.
Due to the presence of negative-sequence components in both the output current and grid voltage, when transformed to the positive synchronous reference frame under conventional control, the d-axis component ed, q-axis component eq, output current d-axis component id, and q-axis component iq all consist of DC components superimposed with second-harmonic AC components. Traditional PI controllers cannot achieve zero steady-state error tracking for AC quantities. Consequently, the calculated inverter output voltages vd and vq contain second-harmonic components. When transformed back to the three-phase stationary frame, these manifest as third-harmonic components. Thus, the solar inverter output voltage contains third-harmonic content, which in turn produces third-harmonic currents in the output.
Table 2 summarizes the key differences I identified between symmetrical and asymmetrical fault responses in grid-connected solar inverters.
| Characteristic | Symmetrical Fault | Asymmetrical Fault |
|---|---|---|
| Sequence Components | Positive-sequence only | Positive and negative sequence |
| Power Oscillation | None | 2nd harmonic (100 Hz) |
| DC Bus Voltage | Rises (high irradiance) | 2nd harmonic ripple |
| Current Limitation | Effective | Ineffective per-phase |
| Harmonic Distortion | Minimal | 3rd harmonic present |
| MPPT Interference | May stop | Unaffected |
DC-Side Voltage Fluctuation Effects
Based on the control strategy I examined, during normal operation of the solar inverter, the modulation wave amplitude is adjusted to maintain constant output voltage amplitude despite variations in DC bus voltage. When a second-harmonic fluctuation occurs in the DC bus voltage during asymmetrical faults, the calculated modulation wave amplitude also fluctuates at the second-harmonic frequency, but these two fluctuations tend to cancel each other. Therefore, I concluded that DC bus voltage fluctuation does not cause third-harmonic content in the output voltage as it would in general-purpose inverters.
My theoretical analysis indicated that under the conventional control strategy, the third harmonic in the solar inverter output voltage stems from the PI controller’s inability to achieve zero steady-state error tracking of AC components, not from DC bus voltage fluctuation. To verify this hypothesis, I modified the conventional control strategy by incorporating a second-order notch filter to remove the second-harmonic ripple from the calculated vd and vq without implementing any negative-sequence control.
Regarding the maximum power point tracking control, in high-power single-stage solar inverters, the perturbation and observation method typically updates the DC voltage reference every few hundred milliseconds. This interval far exceeds the period of DC bus voltage disturbance. The MPPT control determines the perturbation direction based on averaged voltage and power values over multiple sampling points, and the averaging process inherently eliminates the effects of DC bus voltage fluctuation and DC-side power oscillation. Thus, these fluctuations do not interfere with MPPT control operation.
Simulation Verification
To validate my theoretical analyses, I constructed an electromagnetic transient model of the grid-connected solar inverter system shown in the system configuration using PSCAD/EMTDC. In my simulations, a fault occurred at t = 4 seconds at the point of interconnection, causing voltage sag that persisted for 2 seconds until fault clearance at t = 6 seconds. I assumed that all inverter protection systems remained inactive during the fault to observe the full dynamic response.
Symmetrical Fault Results
For the symmetrical fault case, I simulated a three-phase fault causing the POI voltage to drop to 0.5 pu (voltage base of 220 V). I investigated two operating conditions: high irradiance (1500 W/m²) and low irradiance (1000 W/m²).
Under high irradiance conditions, before the fault, the system operated normally with the DC bus voltage gradually decreasing, output power increasing, and the solar inverter delivering approximately 345 kW with the output current d-axis component at approximately 0.69 pu and q-axis component at 0. At t = 4 seconds, when the fault occurred and the POI voltage dropped to 0.5 pu, the maximum power output limit became 275 kW, which was lower than the pre-fault power. This caused the DC bus voltage to rise, the output current d-axis component to increase to 1.1 pu, and the output power to stabilize at 275 kW. After fault clearance at t = 6 seconds, the inverter resumed its pre-fault operating state.
Under low irradiance conditions, the pre-fault output power was approximately 235 kW with the output current d-axis component at about 0.45 pu. Since this was below the fault-time output power limit of 275 kW, the output current d-axis component increased to only 0.9 pu during the fault. The MPPT control continued operating normally, and the DC bus voltage and output power variations remained essentially unaffected by the fault.
These simulation results confirmed my theoretical prediction that during symmetrical faults, the working state of the photovoltaic array is determined by the solar inverter’s power delivery capability.
Asymmetrical Fault Results
For the asymmetrical fault case, I simulated a fault causing the POI positive-sequence voltage to drop to 0.75 pu with a negative-sequence voltage of 0.25 pu. Table 3 presents the key observed behaviors of the solar inverter during this period.
| Quantity | Observed Behavior |
|---|---|
| DC Bus Voltage | 100 Hz ripple component |
| DC-side Power | 2nd harmonic oscillation |
| Output Active Power | 2nd harmonic oscillation |
| dq-axis Currents | 2nd harmonic ripple contained |
| Three-phase Currents | Phase b and c overcurrent |
| Modulation Wave | 3rd harmonic content |
| Output Current | 3rd harmonic distortion |
My simulation results demonstrated that during the asymmetrical fault, the presence of negative-sequence current and voltage caused the solar inverter’s output power to fluctuate at twice the fundamental frequency, with corresponding second-harmonic fluctuations in the DC-side power and DC bus voltage. Notably, although the dq-axis current components did not show overcurrent, the three-phase output currents in phases b and c exceeded the rated values. This confirmed that the conventional control strategy’s current limitation cannot restrict each individual phase current when negative-sequence components are present.
The simulation also revealed that the inverter output current dq-axis components and output voltage dq-axis components both contained second-harmonic ripple. The calculated modulation wave contained third harmonics, which consequently produced third-harmonic voltage and current in the solar inverter output.
To further verify that the third harmonic generation is independent of DC bus voltage fluctuation, I implemented the modified control strategy with second-order notch filters. The results showed that although the DC bus voltage still contained the 100 Hz ripple due to negative-sequence components, the output voltage dq-axis components after the notch filter had their second-harmonic components essentially eliminated. The modulation wave and output current no longer contained third harmonics. This confirmed that using a varying sinusoidal wave to modulate against the fluctuating DC voltage eliminates the influence of DC voltage variation on the inverter output voltage.
Regarding MPPT operation during the asymmetrical fault, my simulation showed that before t = 4 seconds, the DC bus voltage was continuously decreasing and the DC-side power was continuously increasing, indicating normal MPPT tracking. During the 4-6 second fault period, apart from the transient processes at fault initiation and clearance, the DC bus voltage continued decreasing according to the original pattern and the DC-side power continued increasing. This confirmed that the MPPT control remained unaffected by the fault conditions.
Conclusions
Through my comprehensive theoretical analysis and simulation verification of grid-connected solar inverters under various power grid fault conditions, I have reached the following important conclusions:
First, during symmetrical grid faults, the current limiting of solar inverters restricts their power delivery capability, which in turn determines whether the photovoltaic array operating point must change. Under high irradiance conditions where the pre-fault power exceeds the fault-time delivery limit, the MPPT control ceases operation and the DC bus voltage rises. Under low irradiance conditions where the pre-fault power remains below the delivery limit, the MPPT control continues operating normally.
Second, during asymmetrical grid faults, the output current of solar inverters contains substantial negative-sequence components. These negative-sequence currents cause second-harmonic oscillations in both the DC bus voltage and DC power. Because the three-phase currents become unbalanced, the current limitation in conventional control strategies cannot effectively restrict each individual phase current, potentially leading to overcurrent in specific phases.
Third, the third-harmonic content in the solar inverter output current during asymmetrical faults originates from the traditional PI controller’s inability to achieve zero steady-state error tracking of AC quantities, not from the DC bus voltage second-harmonic fluctuation. My modified control strategy with notch filters confirmed this conclusion by eliminating the third harmonic without addressing the DC voltage ripple.
Fourth, the second-harmonic fluctuations in DC bus voltage and DC power do not interfere with MPPT control operation. The averaging processes inherent in MPPT algorithms effectively filter out these oscillatory components, allowing the maximum power point tracking to proceed undisturbed during asymmetrical fault conditions.
My research provides valuable insights into the dynamic behavior of grid-connected solar inverters during various grid fault scenarios. These findings serve as a foundational reference for the design of low voltage ride-through control strategies for large and medium-scale grid-connected solar inverters, as well as for the operational planning of large photovoltaic power stations interconnected to the grid.
The understanding gained from this work is essential for developing enhanced control schemes that can improve the fault ride-through capability of solar inverters. Future research directions may include the development of coordinated positive and negative sequence control strategies, active power oscillation suppression techniques, and reactive power support algorithms during asymmetrical faults. These advancements will contribute to the reliable and stable integration of solar photovoltaic power into modern power systems, supporting the global transition toward sustainable energy sources.
In summary, my theoretical framework and simulation results offer a comprehensive understanding of how grid-connected solar inverters respond to both symmetrical and asymmetrical power grid faults. The key differentiators I identified—power delivery capability for symmetrical faults and negative-sequence component effects for asymmetrical faults—provide clear guidance for inverter manufacturers and system operators. By addressing these specific challenges, the low voltage ride-through performance of solar inverters can be significantly improved, ensuring the continued growth and stability of solar power generation in the evolving energy landscape.