Charge Throughput Suppression Strategy of the Modular Multilevel Converter-Battery Energy Storage System for the Medium-Voltage DC Distribution Network

The integration of renewable energy sources and advanced power electronics in modern grids has heightened the demand for efficient energy storage solutions. Modular multilevel converter-battery energy storage systems (MMC-BESS) have emerged as a critical technology for medium-voltage DC (MVDC) distribution networks. However, periodic power fluctuations in submodules lead to frequent charge-discharge state transitions in battery packs, generating additional charge throughput that accelerates battery degradation. This challenge becomes more pronounced when MMC-BESS interfaces with solar inverters and other renewable energy systems, where bidirectional power flow and variable operating conditions exacerbate charge throughput issues.

System Modeling and Charge Throughput Analysis

The MMC-BESS topology consists of cascaded submodules with embedded battery units, enabling bidirectional power transfer between AC/DC grids. The charge throughput \( Q \) is defined as:

$$ Q = \int_{0}^{T} |i_{\text{bat}}| \, dt $$

where \( i_{\text{bat}} \) is the battery current and \( T \) is the grid cycle period. Key factors influencing \( Q \) include:

  1. Modulation ratio \( m \)
  2. Energy storage power ratio \( k = P_{\text{bat}}/P_{\text{ac}} \)
  3. Circulating current characteristics

For a three-phase MMC-BESS with \( N \) submodules per arm, the arm currents are expressed as:

$$
\begin{cases}
i_{\text{ua}} = I_{\text{cira}} + \frac{I_m}{2}\cos(\omega t + \phi) + \lambda I_m\cos(2\omega t + \theta) \\
i_{\text{la}} = I_{\text{cira}} – \frac{I_m}{2}\cos(\omega t + \phi) + \lambda I_m\cos(2\omega t + \theta)
\end{cases}
$$

where \( \lambda \) and \( \theta \) represent the amplitude and phase angle of injected second-order circulating currents.

Optimal Circulating Current Injection Strategy

The proposed strategy minimizes charge throughput through optimized second-harmonic current injection. The optimal parameters (\( \lambda_{\text{opt}}, \theta_{\text{opt}} \)) are determined by solving:

$$
\min_{\lambda, \theta} \sum_{x=u,l} \int_{0}^{T} |S_x(t)i_x(t)| \, dt
$$

where \( S_x(t) \) represents the switching function of submodules. The solution space for different operating conditions is shown below:

Optimal Circulating Current Parameters
Operating Mode \( k \) Range \( \lambda_{\text{opt}} \) \( \theta_{\text{opt}} \) (rad)
Battery Charging (Inverter) 0.2-0.8 0.12-0.35 0
Battery Discharging (Inverter) -0.5-0 0.25-0.45 0
Grid Support (Solar Inverter Mode) -1.0-1.0 0.18-0.32 \(\pi/6\)

Simulation and Experimental Validation

The control strategy was tested under multiple scenarios relevant to solar inverter applications:

Charge Throughput Reduction Performance
Case \( P_{\text{ac}} \) (MW) \( k \) Reduction
Inverter Charging 5 0.2 37.6%
Inverter Discharging 5 -0.2 24.5%
Solar Inverter Integration 3 0.5 31.2%

The experimental platform with 4 submodules per arm demonstrated:

$$
Q_{\text{reduction}} = \frac{Q_{\text{base}} – Q_{\text{optimized}}}{Q_{\text{base}}} \times 100\% = 31.5\% \text{ (at } k = -0.2)
$$

Implementation Considerations for Solar Inverter Systems

When integrated with solar inverters, the MMC-BESS requires additional adaptations:

  1. Dynamic \( k \) adjustment based on PV generation
  2. Harmonic compensation for variable DC-link voltage
  3. Enhanced SOC balancing for partial shading conditions

The system efficiency when combined with commercial solar inverters follows:

$$
\eta_{\text{total}} = \eta_{\text{MMC}} \times \eta_{\text{inv}} = 97.2\% \times 98.5\% = 95.7\%
$$

Conclusion

The proposed second-harmonic injection strategy effectively suppresses charge throughput in MMC-BESS, particularly in solar inverter applications with variable power flow. Future work will focus on real-time parameter adaptation and integration with multi-port solar inverter topologies.