The global transition in energy infrastructure and increasing urgency for environmental protection have propelled photovoltaic (PV) power generation into widespread adoption. PV systems convert solar energy into electricity, which is then fed into the grid through a grid tied inverter. However, a critical challenge affecting system stability and efficiency is the imbalance of voltages on the DC side of the inverter. Conventional control models for this purpose are often structured independently, leading to numerous operational constraints and, ultimately, increased voltage deviation. This article delves into the design and research of a novel DC voltage balance control method for grid tied inverter systems, aiming to overcome these limitations.
1. The Problem of DC-Link Voltage Imbalance
In a three-phase grid tied inverter, particularly those with topologies like the Neutral-Point-Clamped (NPC) inverter, the DC-link is typically split by capacitors to create a neutral point. Under ideal, balanced conditions, the voltages across these capacitors are equal. However, in practical PV applications, several factors disrupt this balance:
- Inherent Asymmetries: Slight manufacturing tolerances in switching devices and passive components.
- Unbalanced Grid Conditions: Grid voltage sags, swells, or phase imbalances.
- Unbalanced Loads or Generation: Partial shading on PV arrays or unequal power generation from different strings.
This voltage imbalance leads to several detrimental effects: increased voltage stress on semiconductor devices, higher total harmonic distortion (THD) in output currents, and the injection of undesirable low-frequency currents into the PV array, reducing overall efficiency and potentially causing premature component failure. Therefore, an effective balancing control strategy is paramount for the reliable operation of a grid tied inverter.

2. Design of the Proposed Multi-Objective Balancing Control Method
The proposed methodology breaks away from conventional independent control loops by integrating calculations for average power, constructing a decoupled per-phase control structure, and implementing a bidirectional switching logic for seamless operation under various grid conditions.
2.1 Average Power Calculation and Reference Generation
The foundation of the control strategy is the accurate computation of power components. When the grid is unbalanced, the inverter must inject both zero-sequence and negative-sequence voltage/current components to regulate power flow and manage the DC-link voltages. The instantaneous power theory is extended to calculate the required adjustable active power component needed for balancing.
The variable active power required to counteract the imbalance caused by oscillatory power terms is calculated. Under unbalanced grid voltages, the active power has a double-line-frequency oscillatory component. To mitigate its effect on the DC-link, a compensating active power signal is derived. The expression for this variable active power component, $\Delta P$, is given by:
$$ \Delta P = \frac{3}{2} \cdot \frac{Q \cdot E \cdot \mu}{\omega L} $$
where $Q$ represents the magnitude of the injected zero-sequence voltage component, $E$ is the grid voltage magnitude, $\mu$ is the modulation index difference reflecting the voltage imbalance, $\omega$ is the grid angular frequency, and $L$ is the filter inductance. This $\Delta P$ is used to generate a reference for the balancing controller.
Subsequently, the average power over a fundamental cycle, $K_{avg}$, which serves as a stable reference for the overall power control loop, is calculated by integrating the instantaneous power and filtering the oscillatory components. A simplified representation for setting the reference in the control loop is:
$$ K_{avg} = P_{ref} – \frac{v \cdot (g_1^2 – g_2^2)}{2\omega L} + \frac{O^2}{6\omega L} $$
Here, $P_{ref}$ is the total active power command, $v$ is the measured DC-link voltage error, $g_1$ and $g_2$ are the positive and negative sequence grid voltage components, and $O$ is the zero-sequence component. This calculation ensures the control system has a robust target amidst grid disturbances.
2.2 Constructing the Decoupled Per-Phase Control Structure
Traditional voltage-oriented control in a grid tied inverter treats the system in the synchronous rotating dq-frame, which couples the phases. The proposed method employs a per-phase control structure. This structure directly controls the phase voltages to be in phase (or anti-phase) with the corresponding grid phase voltages, offering more straightforward handling of imbalances.
The key is to inject specific current harmonics. By strategically injecting a combination of zero-sequence and negative-sequence current components into the three-phase currents, independent control of the power flow in each phase branch of the inverter is achieved. This allows for direct adjustment of the power drawn from or supplied to each half of the DC-link.
The per-phase reactive current component, $S_{\phi}$ (where $\phi = a, b, c$), required for this decoupled control is derived from a vector analysis of the inverter currents. It is calculated to ensure that the active power flow for each phase can be adjusted independently to balance the capacitor voltages. The expression is:
$$ S_{\phi} = \gamma \cdot \left( O_{\phi} – \frac{j_{\phi} \cdot \eta_{\phi}}{\sqrt{3}} \right) + \zeta_{\phi} $$
where $\gamma$ is a control gain related to the system period, $O_{\phi}$ is the per-phase DC-link voltage measurement, $j_{\phi}$ and $\eta_{\phi}$ are the zero-sequence and negative-sequence voltage components for the phase, and $\zeta_{\phi}$ is the per-phase adjustment term from the balancing controller. This structure provides greater flexibility and a wider control range compared to traditional coupled designs. A summary of key parameters for the per-phase control setup is provided below.
| Control Parameter | Symbol | Typical Value / Range |
|---|---|---|
| Phase Lock Loop Angle | $\theta$ | 45° (for initial synchronization) |
| Steady-state Voltage Vector Magnitude | $V_{ss}$ | 13.72 (p.u.) |
| Per-Phase Control Loop Bandwidth | $BW_{phase}$ | 2.44 Hz |
| Control Unit Processing Delay | $T_d$ | 0.17 s |
| Target Per-Phase DC Voltage | $V_{dc,\phi}$ | 220 V |
2.3 Multi-Objective Control Model and Bidirectional Switching Logic
The core innovation is the multi-objective control model. Instead of having a single objective (e.g., balance the capacitors), the controller simultaneously manages:
1. Total active power delivery ($P_{total}$).
2. Total reactive power compensation ($Q_{total}$).
3. DC-link voltage balance ($\Delta V_{dc}$).
4. Current harmonic distortion minimization (THD).
This is formulated as an optimization problem where the control outputs (modulation signals) are adjusted to minimize a cost function, $J$:
$$ J = \alpha (P_{ref} – P_{meas})^2 + \beta (Q_{ref} – Q_{meas})^2 + \chi (\Delta V_{dc})^2 + \delta (THD_i)^2 $$
Here, $\alpha, \beta, \chi, \delta$ are weighting factors that prioritize the objectives based on system requirements. The grid tied inverter control algorithm solves this in real-time to determine the optimal switching commands.
To handle the distinct requirements under balanced vs. severely unbalanced grid faults, a bidirectional switching balance discriminator is implemented. This logic monitors grid symmetry indices and DC-link imbalance. Based on predefined thresholds, it switches between two control modes:
- Mode A (Normal/Mild Imbalance): Employs the per-phase control with minimal zero/negative sequence injection, focusing on efficiency and THD.
- Mode B (Severe Imbalance/Fault): Prioritizes DC-link balance and grid support. It actively injects calculated zero and negative sequence currents as per the multi-objective model to maintain capacitor voltage balance even during large asymmetries.
The switching logic ensures the grid tied inverter always operates in the most appropriate control regime, enhancing robustness.
3. Method Validation and Testing
The proposed control method for the grid tied inverter was validated through detailed simulation studies to compare its performance against conventional methods.
3.1 Test Setup and Simulation Environment
A simulation model was built using PSPICE 8.0. The main circuit consisted of a three-phase uncontrolled rectifier feeding an NPC inverter, which is connected to the grid through an L filter. The switching was managed via a carrier-based PWM scheme. Key circuit parameters were set to reflect a realistic medium-power grid tied inverter scenario, as detailed below.
| Parameter | Value |
|---|---|
| Grid Line-to-Line Voltage | 360 V |
| Grid Frequency | 50 Hz (45-55 Hz range tested) |
| Grid-side Filter Inductance | 3 mH (2-3.5 mH range) |
| DC-Link Capacitance (each half) | 6000 µF (5200-6800 µF range) |
| DC-Link Voltage Command | 380 V (320-440 V range) |
| Carrier Frequency | 2.0 kHz (1.6-2.2 kHz range) |
| Bidirectional Mode Switching Time | 0.1 s |
3.2 Test Process and Results Analysis
The system was subjected to stringent tests, including sudden load changes and severe grid voltage imbalances. A key test involved applying a sudden unbalanced load increase on the DC-side to create a severe voltage imbalance between the capacitors. The response of the DC-link voltages is shown in the following conceptual graph, demonstrating the controller’s ability to restore balance rapidly.
[Simulation result showing capacitor voltages Vc1 and Vc2 diverging upon a load step and converging back to balance with the proposed controller].
The load difference, $F_{diff}$, between the upper and lower DC-link paths was calculated during the transient to quantify the imbalance severity:
$$ F_{diff} = \frac{|m – n|}{\alpha} \cdot \frac{1}{y} $$
where $m$ and $n$ are the instantaneous load powers on each DC-link half, $\alpha$ is the nominal load, and $y$ is the number of sampling cycles within the imbalance event.
The controller’s performance was further assessed by comparing the voltage and current waveforms before and after the load disturbance. The proposed method maintained sinusoidal currents with low distortion even during the balancing action, unlike conventional methods which often show significant distortion during such transients.
[Waveforms comparing pre-fault and post-fault grid currents and phase voltages, highlighting maintained quality with the new method].
The ultimate metric for evaluation is the Balance Control Voltage Deviation (BCVD), $J_{v}$. It is defined as the normalized RMS difference between the two capacitor voltages over the disturbance period, factoring in the system’s dynamic response:
$$ J_{v} = \frac{1}{\lambda \cdot \phi} \int_{0}^{\varrho} \left| \frac{W_1(t) – W_2(t)}{\phi} \right|^2 dt $$
Here, $W_1(t)$ and $W_2(t)$ are the instantaneous voltages of the two DC-link capacitors, $\phi$ is the nominal DC-link voltage, $\lambda$ is the fundamental frequency, and $\varrho$ is the total response and evaluation time window.
Three different test circuits (A, B, C) with varying component tolerances and grid impedances were simulated. The BCVD was measured for each under two critical conditions: when the controller was tasked to balance voltages by injecting primarily 1) a zero-sequence voltage and 2) a negative-sequence voltage. The results conclusively demonstrate the superiority of the proposed multi-objective, per-phase control method.
| Test Circuit Configuration | BCVD with Zero-Sequence Injection ($J_{v,z}$) | BCVD with Negative-Sequence Injection ($J_{v,n}$) |
|---|---|---|
| Circuit A (High Imbalance) | 1.12 | 1.24 |
| Circuit B (Medium Imbalance) | 1.03 | 1.07 |
| Circuit C (Low Imbalance) | 1.05 | 1.13 |
Analysis: For all three test circuits, under both injection strategies, the measured BCVD remains below 1.5. This low and consistent deviation value, significantly lower than what is typically achieved with conventional independent control models, validates the effectiveness of the proposed method. It confirms that the designed DC voltage balance control method for grid tied inverter systems is more efficient and provides substantially improved control performance under a wide range of operating conditions.
4. Conclusion
This article has presented a comprehensive design and analysis of an advanced DC-link voltage balancing control method for photovoltaic grid tied inverter systems. By moving beyond conventional models through the integration of average power calculation, a decoupled per-phase control structure, and a multi-objective optimization framework with bidirectional mode switching, the proposed strategy effectively addresses the limitations of prior approaches. The simulation results demonstrate a marked reduction in voltage deviation during unbalanced transients, leading to enhanced system stability, improved power quality, and increased operational reliability. This advancement contributes directly to the optimization of PV system performance, supporting the broader integration of clean, efficient solar energy into the modern power grid and aiding the global transition towards a sustainable energy future.
