With the rapid development of photovoltaic power generation in China, the cumulative installed capacity of photovoltaic power plants reached 77,420 MW by the end of 2016. As the proportion of photovoltaic capacity in the power system continues to grow, a thorough understanding of the low voltage ride-through (LVRT) behavior of inverters has become essential for assessing the impact of photovoltaic stations on the grid. In this paper, we present a comprehensive investigation into the LVRT characteristics of photovoltaic inverters, focusing on the identification of dominant control stages and the development of a practical parameter testing methodology. Our work is motivated by the fact that inverter manufacturers rarely disclose their internal control strategies and parameters, making it a challenging “gray-box” problem to analyze LVRT performance. We structure the inverter as three interconnected functional stages: the DC voltage conversion stage, the AC current command stage, and the AC current response stage. Through time-domain electromagnetic transient simulations, we demonstrate that the AC current command stage is the dominant factor determining the AC-side transient characteristics. Based on this finding, we propose a generalized parameter testing approach that sequentially identifies the reactive current and active current command parameters. The proposed method is validated through experiments on both a string inverter and a centralized inverter, showing excellent agreement between measured and simulated responses. Our results confirm that the parameter testing method is both adaptable and effective for different inverter topologies.
1. Introduction
The analysis of low voltage ride-through characteristics of photovoltaic inverters plays a fundamental role in evaluating grid stability under fault conditions. Photovoltaic systems are required to remain connected to the grid during voltage sags and provide reactive current support to help restore grid voltage. The behavior of inverters during these events is governed by complex internal control algorithms that are typically proprietary. This creates a significant challenge for grid operators and researchers who need accurate models for stability studies.
Existing research has largely focused on inverter control strategies under known parameters. For instance, some studies have proposed LVRT control strategies for centralized inverters, where the control strategy switches between normal and fault-ride-through modes, limiting active current and injecting reactive current during the fault. Other studies have derived steady-state short-circuit current calculation formulas based on power control objectives. However, these approaches presuppose that the control strategy and parameters are known, which is rarely the case in practice.
For string inverters, most prior work has concentrated on conversion efficiency, cost, reliability, and harmonic suppression, with limited attention to LVRT characteristics. Standardization efforts such as the German FGW TG3 and TG4 guidelines, as well as the Chinese national standard GB/T 32892-2016, provide general principles for electrical characteristic testing, model validation, and parameter identification. However, these standards do not specify detailed identification algorithms. In our previous work, we addressed parameter identification for typical dual-loop control structures, but the critical factor of switching to LVRT-specific control during voltage sags was not fully considered.
In this paper, we bridge this gap by analyzing the physical LVRT process and identifying the key control stage that dominates the transient response. We then propose a systematic parameter testing method tailored to this dominant stage, and verify it experimentally. Our approach is designed to be generic, applicable to both string and centralized inverters, and does not require any proprietary knowledge of the inverter’s internal control logic.
2. Topology and Control Strategy of Photovoltaic Inverters
2.1 Topological Structures
Photovoltaic inverters can be broadly classified into centralized and string types. Centralized inverters come in single-stage and dual-stage configurations. In a single-stage centralized inverter, maximum power point tracking (MPPT) and inversion are performed in a single power conversion stage, while a dual-stage design includes a separate DC-DC converter for MPPT. String inverters, on the other hand, are available as single-string or multi-string versions, differing mainly in the number of PV strings connected to the DC side.
Despite these differences, the overall topologies are quite similar. Both centralized and string inverters employ a DC-AC conversion stage with an LCL or LC filter, and both can exhibit controlled current source behavior under grid-voltage-oriented dq-axis decoupling control. The primary distinction lies in the DC-side architecture and the power rating. A typical string inverter uses multiple independent Boost converters feeding a common DC bus, with each Boost converter performing MPPT for its associated PV string. This arrangement prevents power mismatch between strings. In contrast, a centralized inverter handles the entire PV array as a single MPPT unit.
3. Control Strategy Decomposition
To analyze the LVRT behavior in a systematic manner, we decompose the inverter into three functional stages regardless of its specific topology or manufacturer:
- DC voltage conversion stage: This stage includes all DC-DC converters, such as Boost circuits, that perform MPPT and regulate the DC bus voltage. The control objective is to maintain the PV string voltage at its maximum power point under normal operation.
- AC current command stage: This stage generates the active and reactive current references (d-axis and q-axis) that the inverter must inject into the grid. During LVRT, this stage follows a fault-ride-through control strategy that may limit active current and inject reactive current proportional to voltage deviation.
- AC current response stage: This stage consists of the inverter bridge and its current control loop, which ensures that the actual output currents track the reference commands. Common topologies include two-level half-bridge, diode-clamped three-level, and T-type three-level circuits.
By separating the inverter into these three stages, we can independently assess their influence on the LVRT dynamic response. The control strategy during normal operation is based on grid-voltage-oriented vector control, with the d-axis representing active power and the q-axis representing reactive power. When a grid fault occurs, the MPPT is disabled, and the inverter switches to a dedicated LVRT control mode. The DC voltage feedback is introduced to suppress overvoltage on the DC bus. The duty cycle of the Boost converter during the fault is given by:
$$ d = d_0 – K_{U_{dc}}(U_{dc} – U_{dc,\max}) $$
where \( d_0 \) is the pre-fault duty cycle, \( K_{U_{dc}} \) is the proportional control coefficient, \( U_{dc} \) is the measured DC bus voltage, and \( U_{dc,\max} \) is the maximum allowable DC voltage.
The current references during the fault are computed as follows:
$$ i_{d,ref} = I_{d,LVRT} $$
$$ i_{q,ref} = \min\left( K_{q,LV}(0.9 – U_{term}), I_{\max} \right) $$
Here, \( I_{d,LVRT} \) is the active current setpoint, \( K_{q,LV} \) is the reactive current support coefficient, \( U_{term} \) is the AC terminal voltage in per unit, and \( I_{\max} \) is the maximum allowable current. After fault clearance, the q-axis reactive current reference returns to its pre-fault value immediately, while the d-axis active current reference recovers at a finite slope defined by \( K_{id,ref} \).
4. Low Voltage Ride-Through Physical Process
During an LVRT event, the inverter experiences a sequence of control mode transitions: from normal control to LVRT control and back to normal control. The operating point undergoes wide excursions. Immediately after the fault, the AC current command stage produces new current references, and the AC current response stage tracks them within approximately 10 ms. For bulk power system studies, this fast response can be simplified by assuming that the actual currents equal the reference currents:
$$ P = \frac{3}{2} u_d i_d \approx \frac{3}{2} u_d i_{d,ref} $$
$$ Q = \frac{3}{2} u_d i_q \approx \frac{3}{2} u_d i_{q,ref} $$
where \( P \) and \( Q \) are active and reactive power, \( u_d \) is the d-axis voltage component, and \( i_d \) and \( i_q \) are the d- and q-axis currents.
The DC bus capacitor couples the PV input power and the inverter output power:
$$ C U_{dc} \frac{dU_{dc}}{dt} = P_{PV} – P $$
When a voltage sag occurs, \( P \) drops abruptly, causing a power imbalance across the DC capacitor, and \( U_{dc} \) rises. For a Boost converter, the relationship between PV string voltage \( U_{PV} \) and DC bus voltage is \( U_{PV} = (1-d) U_{dc} \). Since the duty cycle controller has a finite bandwidth, \( U_{PV} \) also increases, shifting the PV array operating point away from the maximum power point. The PV output power then settles at a new reduced value. Under the action of the DC controller, the inverter eventually reaches a quasi-steady-state during the fault.
After fault clearance, the control mode reverts to normal, and the inverter gradually recovers its pre-fault state. From this physical description, we can draw three key observations:
- The AC current command stage directly determines the AC-side current and power output, and the AC current response stage tracks these commands quickly.
- The DC voltage conversion stage responds to AC power changes through the DC bus capacitor coupling, but its influence on AC quantities is secondary.
- Reactive power \( Q \) is only weakly coupled to the DC voltage conversion stage.
5. Influence of Each Stage on LVRT Characteristics
Because LVRT behavior is nonlinear and discrete, linearized models are inadequate. We therefore employed electromagnetic transient (EMT) simulation models in MATLAB/Simulink for both a three-string inverter and a single-stage centralized inverter. The main parameters of these models are summarized in the following tables.
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated power | 36 kW | DC bus voltage | 1000 V |
| Rated grid voltage | 480 V | DC bus capacitor | 900 µF |
| Input capacitor (DC) | 300 µF | AC filter inductance | 5.1 mH |
| Input inductance (DC) | 3 mH | Inverter switching frequency | 10 kHz |
| Output capacitor (DC) | 300 µF | DC-DC switching frequency | 20 kHz |
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated power | 500 kW | Filter inductance | 0.18 mH |
| Rated grid voltage | 270 V | Inverter switching frequency | 3 kHz |
| DC bus capacitor | 14.4 mF | Maximum DC voltage | 1000 V |
5.1 Impact of the DC Voltage Conversion Stage
Since the single-stage centralized inverter has no separate DC-DC stage, this analysis was performed on the string inverter model. We defined four parameter sets for the DC voltage conversion stage as listed in Table 3.
| Parameter set | \( U_{dc,\max} \) (V) | \( K_{U_{dc}} \) |
|---|---|---|
| A1 | 1050 | 0.001 |
| A2 | 1000 | 0.001 |
| A3 | 950 | 0.001 |
| A4 | 950 | 0.002 |
Figure 2 in the original paper showed the impact of the DC voltage conversion stage. We summarize our findings as follows:
- The DC voltage conversion stage significantly affects the DC bus voltage \( U_{dc} \). Smaller \( U_{dc,\max} \) and larger \( K_{U_{dc}} \) lead to less overvoltage. Parameter set A4 resulted in the lowest DC voltage during the fault, limited to below 1030 V.
- The influence on AC-side active and reactive power output, as well as PV string voltage \( U_{PV1} \), is small. The responses of \( P \) and \( Q \) are nearly identical across the four parameter sets due to the galvanic isolation provided by the DC bus capacitor.
- The DC voltage conversion stage affects the overshoot during control mode transitions. Parameter set A1 produced the largest active power overshoot, while A4 produced the smallest.
5.2 Impact of the AC Current Command Stage
We defined three parameter sets for the AC current command stage as shown in Table 4.
| Parameter set | \( I_{d,LVRT} \) | \( K_{q,LV} \) | \( K_{idref} \) (p.u./s) | \( I_{\max} \) |
|---|---|---|---|---|
| B1 | 0.3 | 2 | 1.25 | 1.08 |
| B2 | 0.16 | 1.5 | 2 | 1.08 |
| B3 | 0.16 | 2 | 1.25 | 1.08 |
The results of our simulations (corresponding to Figure 3 in the original) demonstrated that:
- The AC current command stage has a decisive influence on AC-side output power and also strongly affects the DC side because AC active power directly impacts the DC bus power balance.
- A larger active current setpoint \( I_{d,LVRT} \) results in higher active power output during the fault and a shorter recovery time.
- A larger reactive current support coefficient \( K_{q,LV} \) increases reactive power injection during the fault, providing stronger voltage support, but increases the risk of overcurrent.
- A larger active current recovery slope \( K_{idref} \) shortens the fault recovery duration.
5.3 Impact of the AC Current Response Stage
We compared three common inverter output topologies: two-level half-bridge, diode-clamped three-level, and T-type three-level. The simulation results (Figure 4 in the original) showed that the overall DC-side and AC-side responses are nearly identical across these topologies. The main differences are:
- During voltage sags, the diode-clamped and T-type three-level topologies suffer from neutral-point voltage imbalance, causing minor DC voltage oscillations. The half-bridge topology does not have this issue.
- When switching back to normal control, the transient overshoots of voltage and power differ slightly among the topologies.
6. Parameter Testing Method for the AC Current Command Stage
Since the AC current command stage is the dominant factor affecting AC-side transient behavior, we focus our parameter identification efforts on this stage. The proposed method is general and does not rely on proprietary internal information. We set up an experimental test system consisting of a controlled DC source, the inverter under test, and a grid disturbance generator. The test procedure follows the flow chart shown in Figure 5 of the original paper, which we describe here.
6.1 Test Operating Conditions
The inverter is operated under various pre-fault conditions to cover a wide range of possible states:
- Active power levels: high (0.7-1.0 p.u.), medium (0.4-0.6 p.u.), and low (0.1-0.3 p.u.).
- Reactive power outputs: zero reactive power, inductive reactive power (\( Q_L \geq 0.5 Q_{\max} \)), and capacitive reactive power (\( Q_C \geq 0.5 Q_{\max} \)), where \( Q_{\max} \) is the maximum reactive power capability.
Voltage sag levels are set to different residual voltage intervals: 0-0.2, 0.2-0.3, 0.5-0.6, and 0.7-0.9 p.u., with additional test points added as needed.
6.2 Measurement and Consistency Check
We compute the steady-state active and reactive current values before and during the fault. The fault recovery rate of the active current is also recorded. Each test is repeated at least twice to verify repeatability. The measured steady-state currents are assumed to equal the internal reference commands.
6.3 Identification of Reactive Current Command Parameters
The general reactive current command formula during LVRT is expressed as:
$$ I_q = I_{q,ref} = \min\left( K_{q,LV}(U_{LV} – U_{term}) + K_{I_{q0},flag} I_{q0} + I_{q0,LV}, I_{qmax,LV} \right) $$
where:
- \( I_q \) is the reactive current during LVRT.
- \( K_{q,LV} \) is the reactive current support coefficient.
- \( U_{LV} \) is the voltage threshold for entering LVRT control (typically 0.9 p.u. per GB/T 19964-2012).
- \( K_{I_{q0},flag} \) is a flag coefficient indicating whether the pre-fault reactive current is included.
- \( I_{q0} \) is the reactive current before the fault.
- \( I_{q0,LV} \) is the base reactive current during LVRT.
- \( I_{qmax,LV} \) is the maximum allowed reactive current during LVRT.
Known values are \( I_q \), \( I_{q0} \), and \( U_{term} \); the parameters to be identified are \( K_{q,LV} \), \( U_{LV} \), \( K_{I_{q0},flag} \), \( I_{q0,LV} \), and \( I_{qmax,LV} \). We first determine \( I_{qmax,LV} \) by taking the maximum observed reactive current across all tests. For a given voltage sag depth, if the reactive current is the same regardless of the pre-fault reactive power, then \( K_{I_{q0},flag}=0 \); otherwise, \( K_{I_{q0},flag}=1 \). We discard tests where the inverter reaches the current limit. The remaining data then satisfy a linear equation with two unknowns:
$$ I_q = K_{q,LV}(U_{LV} – U_{term}) + K_{I_{q0},flag} I_{q0} + I_{q0,LV} $$
With \( U_{LV} \) known as 0.9 p.u., this becomes a simple linear regression problem. We use the least-squares method to identify \( K_{q,LV} \) and \( I_{q0,LV} \).
6.4 Identification of Active Current Command Parameters
The active current command formula is more complex and depends on a flag \( I_{d,flag} \) that indicates which limiting strategy is active:
$$ I_d = I_{d,ref} = \begin{cases} \min\left( \frac{P_0}{U_{term}}, I_{\max,FRT} – |I_q| \right) & I_{d,flag}=0 \\ \min\left( \frac{P_0}{U_{term}}, \sqrt{I_{\max,FRT}^2 – I_q^2} \right) & I_{d,flag}=1 \\ K_{p1,FRT} I_{d0} + K_{p2,FRT} U_{term} + I_{d0,FRT} & I_{d,flag}=2 \end{cases} $$
where:
- \( I_d \) is the active current during LVRT.
- \( P_0 \) is the pre-fault active power.
- \( I_{\max,FRT} \) is the maximum current during LVRT.
- \( K_{p1,FRT} \) and \( K_{p2,FRT} \) are active current coefficients.
- \( I_{d0} \) is the pre-fault active current.
- \( I_{d0,FRT} \) is the base active current during LVRT.
Known quantities are \( I_d \), \( I_q \), \( P_0 \), \( I_{d0} \), and \( U_{term} \). The parameters to identify are \( I_{\max,FRT} \), \( K_{p1,FRT} \), \( K_{p2,FRT} \), \( I_{d0,FRT} \), and \( I_{d,flag} \). We first determine \( I_{\max,FRT} \) by taking the maximum observed current magnitude across all tests. Then we test each hypothesis for \( I_{d,flag} \).
For \( I_{d,flag}=0 \), we define the residual sum of squares:
$$ RSS_1 = \sum_{i=1}^{n} \left( \min\left( \frac{P_{0,i}}{U_{term,i}}, I_{\max,FRT} – |I_{q,i}| \right) – I_{d,i} \right)^2 $$
For \( I_{d,flag}=1 \):
$$ RSS_2 = \sum_{i=1}^{n} \left( \min\left( \frac{P_{0,i}}{U_{term,i}}, \sqrt{I_{\max,FRT}^2 – I_{q,i}^2} \right) – I_{d,i} \right)^2 $$
For \( I_{d,flag}=2 \), if the active current does not depend on \( I_{d0} \) for the same voltage sag, then \( K_{p1,FRT}=0 \); otherwise \( K_{p1,FRT}=1 \). The formula reduces to a linear regression with unknowns \( K_{p2,FRT} \) and \( I_{d0,FRT} \), allowing us to compute:
$$ RSS_3 = \sum_{i=1}^{n} \left( K_{p1,FRT} I_{d0,i} + K_{p2,FRT} U_{term,i} + I_{d0,FRT} – I_{d,i} \right)^2 $$
The hypothesis with the smallest residual sum of squares is selected. The identified parameters are then substituted into the simulation model for validation.
7. Experimental Validation
7.1 String Inverter Tests
We performed experiments on a three-string inverter rated at 36 kW with a T-type three-level topology. The internal control strategy and parameters were not disclosed. We conducted multiple tests under various operating conditions and measured the steady-state active and reactive currents before and during the fault. The active current recovery rate was measured as 1.25 per second. Using the parameter testing procedure, we identified the following AC current command formulas:
$$ i_{q,ref} = \min(2(0.9 – U_{term}), 1.08) $$
$$ i_{d,ref} = 0.16 $$
We then built an electromagnetic transient model using these formulas. To validate our dominant-stage analysis, we deliberately implemented the AC current response stage with a two-level half-bridge topology (instead of the actual T-type three-level topology) and used typical parameters for the DC voltage conversion stage. Only the AC current command stage matched the actual inverter. If the simulation still matches the measured transient response, it confirms that the AC current command stage is indeed the key dominant stage.
Before the fault, the inverter was operated steadily under high power for more than 10 seconds. The grid voltage was then dropped to the 0.5-0.6 p.u. range. The measured and simulated curves for voltage, current, active power, reactive power, and reactive current are shown in Figure 6(a) of the original paper. The simulation results align closely with the measurements. We quantitatively evaluated accuracy according to the model validation standard, calculating average deviation \( F1 \), transient deviation \( F2 \), maximum steady-state deviation \( F3 \), and weighted deviation \( F_G \). The results are presented in Table 5.
| Interval | Deviation type | Voltage | Current | Active power | Reactive power | Reactive current |
|---|---|---|---|---|---|---|
| A | F1 | 0.0061 | 0.0108 | 0.0057 | 0.0007 | 0.0007 |
| A | F3 | 0.0067 | 0.0117 | 0.0063 | 0.0036 | 0.0036 |
| B1 (transient) | F2 | 0.0004 | 0.0300 | 0.0277 | 0.0219 | 0.0274 |
| B2 (steady) | F1 | 0.0089 | 0.0165 | 0.0006 | 0.0026 | 0.0166 |
| B2 (steady) | F3 | 0.0094 | 0.0174 | 0.0016 | 0.0034 | 0.0177 |
| C1 (transient) | F2 | 0.0031 | 0.0006 | 0.0000 | 0.0110 | 0.0111 |
| C2 (steady) | F1 | 0.0023 | 0.0118 | 0.0086 | 0.0096 | 0.0096 |
| C2 (steady) | F3 | 0.0081 | 0.0143 | 0.0163 | 0.0117 | 0.0116 |
| Overall | F_G | 0.0064 | 0.0136 | 0.0028 | 0.0039 | 0.0117 |
We also tested a deeper voltage sag down to 0-0.2 p.u. The validation results are summarized in Table 6.
| Interval | Deviation type | Voltage | Current | Active power | Reactive power | Reactive current |
|---|---|---|---|---|---|---|
| A | F1 | 0.0032 | 0.0074 | 0.0101 | 0.0021 | 0.0021 |
| A | F3 | 0.0051 | 0.0101 | 0.0115 | 0.0109 | 0.0108 |
| B1 (transient) | F2 | 0.0242 | 0.0783 | 0.0095 | 0.0003 | 0.0283 |
| B2 (steady) | F1 | 0.0018 | 0.0385 | 0.0201 | 0.0021 | 0.0016 |
| B2 (steady) | F3 | 0.0019 | 0.0389 | 0.0202 | 0.0022 | 0.0022 |
| C1 (transient) | F2 | 0.0074 | 0.0015 | 0.0020 | 0.0091 | 0.0100 |
| C2 (steady) | F1 | 0.0017 | 0.0062 | 0.0054 | 0.0088 | 0.0088 |
| C2 (steady) | F3 | 0.0101 | 0.0282 | 0.0281 | 0.0094 | 0.0094 |
| Overall | F_G | 0.0087 | 0.0369 | 0.0108 | 0.0037 | 0.0112 |
These low deviations confirm that the simulation model accurately reproduces the measured LVRT behavior of the string inverter. The results strongly support our conclusion that the AC current command stage dominates the LVRT response, while the AC current response stage and DC voltage conversion stage have secondary effects.
7.2 Centralized Inverter Tests
We also tested a centralized inverter rated at 500 kW, again with undisclosed control parameters. Following the same parameter testing procedure, we identified the following commands:
$$ i_{q,ref} = \min(1.53(0.9 – U_{term}), 1.05) $$
$$ i_{d,ref} = \min\left( \frac{P_0}{U_{term}}, 1.05 – |i_{q,ref}| \right) $$
The measured active current recovery rate was 10 per second. Figure 6(b) in the original paper shows the comparison between measured and simulated waveforms for a fault voltage of 0.5-0.6 p.u. The validation metrics are listed in Table 7.
| Interval | Deviation type | Voltage | Current | Active power | Reactive power | Reactive current |
|---|---|---|---|---|---|---|
| A | F1 | 0.0013 | 0.0054 | 0.0044 | 0.0080 | 0.0080 |
| A | F3 | 0.0028 | 0.0063 | 0.0049 | 0.0085 | 0.0086 |
| B1 (transient) | F2 | 0.0195 | 0.0203 | 0.0068 | 0.0148 | 0.0255 |
| B2 (steady) | F1 | 0.0059 | 0.0154 | 0.0000 | 0.0051 | 0.0156 |
| B2 (steady) | F3 | 0.0084 | 0.0424 | 0.0130 | 0.0120 | 0.0175 |
| C1 (transient) | F2 | 0.0258 | 0.0235 | 0.0468 | 0.0022 | 0.0057 |
| C2 (steady) | F1 | 0.0043 | 0.0056 | 0.0022 | 0.0094 | 0.0094 |
| C2 (steady) | F3 | 0.0116 | 0.0253 | 0.0344 | 0.0099 | 0.0101 |
| Overall | F_G | 0.0044 | 0.0101 | 0.0007 | 0.0068 | 0.0131 |
For the deeper sag to 0-0.2 p.u., the validation results are shown in Table 8.
| Interval | Deviation type | Voltage | Current | Active power | Reactive power | Reactive current |
|---|---|---|---|---|---|---|
| A | F1 | 0.0081 | 0.0135 | 0.0072 | 0.0079 | 0.0080 |
| A | F3 | 0.0090 | 0.0143 | 0.0075 | 0.0086 | 0.0086 |
| B1 (transient) | F2 | 0.0400 | 0.0354 | 0.0083 | 0.0022 | 0.0401 |
| B2 (steady) | F1 | 0.0008 | 0.0334 | 0.0069 | 0.0043 | 0.0326 |
| B2 (steady) | F3 | 0.0019 | 0.0748 | 0.0069 | 0.0101 | 0.0747 |
| C1 (transient) | F2 | 0.0193 | 0.1203 | 0.0948 | 0.0142 | 0.0108 |
| C2 (steady) | F1 | 0.0148 | 0.0152 | 0.0039 | 0.0095 | 0.0097 |
| C2 (steady) | F3 | 0.0330 | 0.0404 | 0.0588 | 0.0099 | 0.0101 |
| Overall | F_G | 0.0164 | 0.0270 | 0.0085 | 0.0056 | 0.0242 |
The results again show very small deviations, confirming that the identified formulas accurately represent the centralized inverter’s LVRT behavior. The parameter testing method is therefore valid for both string and centralized solar inverters.

8. Conclusion
This paper presented a systematic analysis of low voltage ride-through characteristics for photovoltaic inverters and proposed a practical parameter testing method. The inverter was decomposed into three functional stages: DC voltage conversion, AC current command, and AC current response. Through electromagnetic transient simulations, we demonstrated that for both string and centralized inverters, the AC current command stage dominates the AC-side transient response, while the DC voltage conversion stage and AC current response stage have relatively minor influences. A generalized parameter testing method was developed to identify the AC current command parameters without requiring proprietary information from the manufacturer. The method involves performing voltage sag tests under various pre-fault operating conditions, measuring steady-state currents and recovery rates, and using linear regression to fit the command formulas. The identified formulas were validated in simulation models for both a 36 kW string inverter and a 500 kW centralized inverter, with excellent agreement against measured data. Our findings confirm that the parameter testing method is both adaptable and effective for different types of solar inverters. It has already been applied in engineering practice to characterize inverters from multiple brands and models.
The study was performed under strong grid conditions. When the solar inverter is connected to a weak grid, the current control performance may degrade, and the dominant-stage analysis warrants further investigation. Future work will extend the proposed approach to weak grid scenarios and consider the impact of grid impedance on the parameter identification accuracy.