Resilient Distribution Network Energy Storage System Configuration Planning

In my research, I have focused on the configuration planning of energy storage system to enhance the resilience of distribution networks against extreme natural disasters. The increasing frequency and severity of typhoons, rainstorms, ice storms, and earthquakes have posed significant threats to modern power systems. My work is structured around three progressive studies, each addressing different stages of disaster management—pre-disaster planning, in-disaster recovery, and multi-disaster adaptation. Throughout this dissertation, I continuously emphasize the pivotal role of energy storage system in maintaining critical load supply and reducing economic losses.

Chapter 2: Energy Storage Configuration Method Based on Master-Slave Particle Swarm Optimization

In my first study, I proposed a configuration planning method that combines the master-slave mode particle swarm optimization (PSO) algorithm with a comprehensive objective function. The objective function was constructed to consider not only resilience enhancement but also the impact on system network losses and equipment costs. I introduced a resilience index for distribution networks, and all indices were normalized to determine the weights of each sub-objective using the analytic hierarchy process (AHP). The final comprehensive objective function is expressed as:

$$
\min F = \omega_1 f_1′ + \omega_2 f_2′ – \omega_3 f_3′
$$

where \( f_1′ \), \( f_2′ \), and \( f_3′ \) are the normalized values of active power loss, annual investment and operation cost, and the resilience index, respectively. The weights \( \omega_1, \omega_2, \omega_3 \) were obtained via AHP with consistency check.

To improve the computational performance and accuracy of the multi-objective particle swarm optimization, I developed an improved algorithm based on the master-slave (principal-subordinate) mode. In this method, the main particles are treated as leaders, each leading a group of subordinate particles. The mechanism prevents the entire swarm from falling into local optima and significantly reduces the computation time. The update equations for particle velocity and position remain the same as standard PSO:

$$
v_{id}^{(k+1)} = w v_{id}^{(k)} + c_1 r_1 (p_{id}^{(k)} – x_{id}^{(k)}) + c_2 r_2 (g_{d}^{(k)} – x_{id}^{(k)})
$$

$$
x_{id}^{(k+1)} = x_{id}^{(k)} + v_{id}^{(k+1)}
$$

I validated the proposed method on an improved IEEE 33-node distribution network. The simulation considered a typhoon disaster scenario with several line failures. Two scenarios were compared: one without any resilience measure, and another with three battery energy storage system units optimally placed. The results are summarized in Table 1.

Table 1: Comparison of load loss and economic impact under typhoon
Scenario Critical load loss (%) Non-critical load loss (%) Weighted load loss (¥) Network loss (kW)
1: No energy storage 35.7 58.17 693,250 308.7
2: With proposed energy storage system 0 50.89 59,220 195.6

From Table 1, my method successfully protected all critical load nodes and reduced the weighted load loss to only 8.54% of the baseline. The network loss was reduced by 36.6%, demonstrating the dual benefit of energy storage system for resilience and operational efficiency. The program running time was also significantly improved, as shown in Table 2.

Table 2: Program running time comparison
Algorithm Time (seconds)
Traditional multi-objective PSO 750
Proposed master-slave PSO 289

Chapter 3: Resilience Enhancement Strategy Integrating Network Reconfiguration and Mobile Energy Storage

In my second study, I addressed the limitations of the first model by incorporating both network reconfiguration and mobile energy storage system (MESS) into a two-stage resilience enhancement strategy. I first developed a resilience assessment method for grid vulnerability under typhoon disasters. The typhoon wind field was modeled using the Holland model:

$$
v(x,y,t) = v_{\max} \left( \frac{R_{\max}}{r} \right)^b e^{\left[ -\left( \frac{R_{\max}}{r} \right)^a \right]}
$$

where \( v_{\max} \) is the peak wind speed, \( R_{\max} \) is the radius of maximum wind, \( r \) is the distance from the storm center, and \( a \), \( b \) are empirical parameters. Based on this, the failure probabilities of transmission lines and towers were derived using cumulative fault models. I used the impact-increment-based state enumeration (IISE) method to compute the system-level resilience index:

$$
R_{sys} = \sum_{w \in W} P_w \sum_{j=1}^{J} \sum_{s \in \Omega_j} \Delta I_{w,s} \prod_{i \in s} p_{w,i}
$$

This index allows identifying weak branches by calculating branch-level resilience, which is the difference between the system resilience with and without a particular branch failure.

For the pre-disaster stage, I proposed the optimal pre-positioning of mobile energy storage system units near vulnerable nodes. The mobile storage units can perform charging, discharging, and full discharge operations. The key constraints include:

$$
0 \le P_{i,t}^{ch} \le P_{i}^{max}, \quad 0 \le P_{i,t}^{dis} \le P_{i}^{max}
$$

$$
E_{i,t+1} = E_{i,t} + \eta_{ch} P_{i,t}^{ch} \Delta t – \frac{P_{i,t}^{dis} \Delta t}{\eta_{dis}}
$$

$$
SOC_{\min} E_i \le E_{i,t} \le SOC_{\max} E_i
$$

In the in-disaster stage, I developed a dynamic network reconfiguration model combined with mobile energy storage system dispatch. The objective was to minimize the total load shedding during the entire disaster period:

$$
\min f = \sum_{t} \sum_{i} c_i (1 – x_{i,t}) P_{L,i,t}
$$

where \( c_i \) is the load priority weight, \( x_{i,t} \) is the load energization state, and \( P_{L,i,t} \) is the active load at node \( i \) at time \( t \). The network topology constraints were handled using Prim’s algorithm to generate radial configurations.

To solve this complex optimization problem, I integrated reinforcement learning into the particle swarm algorithm, resulting in the self-learning PSO (SLPSO). Each particle could choose among four learning operators: development, jumping out, exploration, and convergence. The selection of operators was determined adaptively via reward functions and selection ratios. This improved algorithm greatly enhanced both the solution quality and the convergence speed.

Simulation results on the IEEE 33-node system with distributed generators and three mobile storage units are presented in Table 3. I compared three recovery schemes:

Table 3: Comparison of disaster recovery schemes
Scheme Cost (¥) Supply percentage – Period 1 (%) Period 2 (%) Period 3 (%) Period 4 (%) Run time (s)
1: Only reconfiguration 14,976 45.15 69.33 74.34 86.33 3,608
2: Only distributed generators 30,612 73.24 – – 83.65 –
3: Proposed reconfiguration + mobile energy storage 32,686 72.83 78.9 91.7 92.1 21.2

My proposed scheme (Scheme 3) achieved the highest supply percentage in every period, with a relatively modest cost increase compared to Scheme 1. The run time was drastically reduced to only 0.5% of Scheme 1’s time. Additionally, I compared mobile energy storage system against fixed storage in terms of economy and resilience, as shown in Table 4.

Table 4: Economic comparison between mobile and fixed energy storage
Category Mobile energy storage system Fixed energy storage system
Number of units 3 9
Total capacity (kWh) 3,000 4,332
Resilience effect (%) 92.1 83.65
Construction cost (10k ¥) 540 1,349.18

It can be observed that mobile energy storage system provides better resilience with only 40% of the fixed storage cost and better utilization, as it can serve other areas during normal periods.

Chapter 4: Energy Storage Configuration Strategy for Multiple Disasters in a Single Region

In my third study, I addressed the limitation of previous resilience assessment methods that required specific fault scenarios. I proposed a quantitative resilience assessment method consisting of two parts: ex-ante and ex-post evaluation. The ex-ante assessment uses a new metric called Performance-Damage-Duration (PDD), which measures the system’s ability to maintain a certain level of supply after losing a percentage of infrastructure for a given duration. The metric is defined as:

$$
X = \frac{1}{Y} \inf \left\{ X \in [0,1] \mid \forall t \in [0,Y], \, \text{system can supply } X \cdot P_{\text{load}} \right\}
$$

This indicator does not depend on any specific event type and therefore can be used to compare the resilience of different systems against various disasters. The ex-post assessment introduces three key indices: total energy not supplied (\( E_{shed} \)), peak load reduction (\( P_{peak} \)), and the resistance-to-recovery ratio (\( R_S \)). These indices together distinguish scenarios that produce identical energy loss but different resilience characteristics.

I validated the proposed resilience assessment using the IEEE 123-node test feeder with different levels and distributions of distributed generation. The ex-ante PDD results are given in Table 5.

Table 5: Ex-ante resilience assessment results
Case Branch-count effect Source redundancy PDD index (%)
1: No DG 131 0.01 9.63
2: 50% DG, 83 small units 131 0.92 53.87
3: 25% DG, 83 small units 131 0.92 21.3
4: 50% DG, 6 large units 131 0.08 28.6
5: 25% DG, 6 large units 131 0.08 19.21

From Table 5, I observed that the PDD index provides meaningful differentiation that traditional metrics (branch-count effect, source redundancy) cannot capture. For example, case 2 has the highest PDD due to high penetration and distributed placement, while case 4 with concentrated DG has lower resilience despite the same capacity.

To solve the storage configuration optimization under multiple disaster scenarios, I introduced the STAR (Star Topology Adaptive Recommender) multi-scenario modeling concept into the particle swarm algorithm. The STAR model learns shared parameters across scenarios and unique parameters for each scenario. For each fully connected layer, the final weights and biases are computed as:

$$
W^p = W^p_{shared} \odot W^p_{private}, \quad b^p = b^p_{shared} + b^p_{private}
$$

In my optimization framework, the first stage (shared scenario) explores the global search space without specific fault data, while the second stage introduces individual disaster fault models (typhoon, rainstorm, ice storm). The results from the first stage feed into the second stage, and a dynamic weight factor adjusts the importance of each scenario based on the success rate from the previous iteration.

I established failure rate models for three extreme natural disasters: typhoon, rainstorm (including landslide, flash flood, and debris flow), and ice storm. For instance, the typhoon-induced tower failure probability is:

$$
\lambda_{m,k,i} = \begin{cases}
0, & v \in [0, v_{d,tower}) \\
e^{-\gamma [v_{m,k,i}(t_i) – 2v_{d,tower}]}, & v \in [v_{d,tower}, 2v_{d,tower}) \\
1, & v \in [2v_{d,tower}, \infty)
\end{cases}
$$

For rainstorm-induced failures, I used fuzzy rules based on risk coefficients from landslide, flash flood, and debris flow, combined with tower vulnerability factors. For ice storm, I developed a stress-state equation to determine conductor stress and tower unbalanced force, leading to failure probability functions.

I then applied the STAR-based two-stage optimization to a modified IEEE 33-node network affected by three disaster scenarios. I compared three schemes:

  • Scheme 1: No distributed energy storage.
  • Scheme 2: Storage installed at maximum load nodes under normal operation.
  • Scheme 3: Storage configured using the proposed single-region multi-disaster strategy.

The ex-ante resilience indices were:

Table 6: Ex-ante resilience index under different schemes
Scheme Ex-ante index (%)
1 12.3
2 32.7
3 55.2

The energy storage system configuration results for Scheme 3 are shown in Table 7.

Table 7: Storage configuration results for Scheme 3
Node Power (kW)
9 206
18 288
22 276
31 230

The ex-post resilience indicators under different disasters for the three schemes are summarized in Table 8.

Table 8: Ex-post resilience metrics under disasters
Disaster Scheme Eshed (kWh) Ppeak (kW)
Typhoon 1 2,962.6 1,907.2
2 2,628.98 1,323.8
3 1,846.65 1,274.5
Rainstorm 1 2,111.3 1,520.4
2 1,905.7 1,102.1
3 1,301.2 910.3
Ice storm 1 2,476.8 1,680.5
2 2,197.4 1,208.6
3 1,512.9 1,010.7

The results demonstrate that my proposed STAR-based multi-scenario configuration (Scheme 3) significantly reduces both total energy not supplied and peak load reduction compared to Schemes 1 and 2. The improvement was about 15% for rainstorm, 13% for ice storm, and 20% for typhoon compared to Scheme 2, while using the same total storage capacity. This proves the effectiveness of the multi-scenario energy storage system configuration in adapting to various unknown disasters.

Conclusions and Future Work

In this dissertation, I have systematically investigated the configuration planning of energy storage system to enhance distribution network resilience. My conclusions are as follows:

(1) The master-slave PSO-based optimization method can effectively locate and size fixed energy storage system to protect critical loads during typhoons, reduce network losses, and minimize investment costs. The proposed algorithm significantly improves computation speed and accuracy compared to traditional multi-objective PSO.

(2) The two-stage resilience enhancement strategy combining dynamic network reconfiguration and mobile energy storage system pre-positioning is highly effective. The mobile storage offers better resilience improvement with much lower cost and higher utilization than fixed storage. The reinforcement learning-based SLPSO algorithm further enhances the solution quality and convergence speed.

(3) The quantitative resilience assessment framework, including pre-event PDD metrics and post-event metrics (Eshed, Ppeak, RS), provides comprehensive and comparable evaluation results across different systems and disaster types. Furthermore, the STAR multi-scenario modeling approach enables a single energy storage system configuration to effectively handle multiple extreme weather events in one region. This greatly reduces the workload of designing resilience measures for each possible disaster.

In the future, I plan to extend the research to more realistic distribution systems with actual geographic and traffic network coupling. The incorporation of repair crew scheduling and detailed time-varying load and renewable generation models will further refine the proposed methods. The ultimate goal is to achieve a truly resilient and adaptive power grid that can withstand the growing challenges of extreme natural disasters.