As the global energy landscape undergoes a profound transformation, the integration of renewable energy sources has become a paramount objective. However, the inherent intermittency of sources such as solar and wind power necessitates the deployment of efficient and reliable energy storage solutions. Among various storage technologies, lithium-ion batteries have emerged as the dominant force, commanding a remarkable 90% market share in the electrochemical energy storage sector, largely due to their superior energy density and extended cycle life. To guarantee the safe and stable operation of these batteries, stringent thermal management is essential. The optimal operating temperature window for lithium-ion batteries is generally considered to be between 20°C and 40°C. Deviations from this range can lead to severe consequences, including accelerated degradation, reduced capacity, and in extreme cases, catastrophic thermal runaway events. Therefore, the development of an advanced thermal management system is not merely an optimization task but a critical safety imperative for the widespread adoption of high-energy-density energy storage batteries.
Current thermal management technologies for energy storage batteries primarily encompass air cooling, indirect liquid cooling, and direct refrigerant cooling. Traditional forced-air convection systems are increasingly encountering performance bottlenecks. Due to the inherently low heat transfer coefficient of air, the cooling capacity per unit area has reached a plateau, rendering them inadequate for meeting the escalating heat dissipation demands of modern, high-capacity battery packs. On the other hand, indirect liquid cooling systems, while offering superior heat transfer performance compared to air, rely on the sensible heat capacity of the coolant. This inherently creates a temperature gradient along the flow path of the cooling plate, as the coolant absorbs heat and its temperature rises. This phenomenon makes it challenging to achieve the stringent temperature uniformity required within a large battery pack. In contrast, direct cooling technology, also known as refrigerant direct cooling, leverages the isothermal phase-change characteristics of refrigerants. By directly evaporating the refrigerant within the cold plates, this method can efficiently absorb heat while maintaining an exceptionally uniform temperature profile across the entire cooling surface. Moreover, the elimination of an intermediate heat exchanger simplifies the system architecture, enhances energy efficiency, and provides a promising pathway for next-generation battery thermal management.
This paper presents a comprehensive experimental investigation into a direct cooling thermal management system specifically designed for energy storage batteries. The system is evaluated under a representative low-heat-load condition, specifically a 500 W heat load per cold plate, which corresponds to a 0.5C charge rate for a typical 1P63S energy storage battery module. The study focuses on characterizing the system’s temperature control capabilities, temperature uniformity, pressure drop characteristics, and overall energy efficiency. Furthermore, a parametric analysis is conducted by varying the compressor operating frequency to identify optimal operational strategies that balance thermal performance against system coefficient of performance (COP). Through this detailed analysis, this work aims to provide valuable insights and design guidance for the advancement of high-efficiency thermal management solutions for energy storage batteries.

System Description and Experimental Setup
The proposed direct cooling thermal management system is a vapor-compression refrigeration cycle specifically adapted for battery thermal management. The core components of the experimental test bench include four battery pack simulators, an air-cooled heat exchanger (condenser), a variable-frequency compressor, a four-way reversing valve, an accumulator, a liquid receiver, a brazed plate heat exchanger, electronic expansion valves, solenoid valves, a refrigerant distributor, and a filter. The system is designed to operate in both cooling and heating modes by switching the four-way valve. The primary focus of this study, however, is on its cooling performance.
In cooling mode, the system operates as follows: high-pressure, high-temperature refrigerant vapor is discharged from the compressor and flows into the finned-tube heat exchanger, which acts as the condenser. Here, the refrigerant rejects heat to the ambient air and condenses into a high-pressure liquid. The liquid refrigerant then passes through the plate heat exchanger for additional subcooling before entering the electronic expansion valve. The expansion valve induces a pressure drop, creating a two-phase mixture at a low temperature and pressure. This refrigerant is then distributed to the direct cooling plates, which serve as the evaporator, where it absorbs heat from the simulated battery modules and vaporizes. The low-pressure vapor exits the cooling plates, passes through the plate heat exchanger to recover some cooling capacity, and returns to the compressor, completing the cycle.
To simulate the heat generation of real batteries, silicone rubber heating pads are employed. Each of the four battery packs consists of a direct cooling plate and a heating pad with a maximum power of 1000 W. The dimensions of a single cooling plate are 1030 mm × 560 mm, with a heat-generating area of 0.47 m². A 1 mm thick thermally conductive pad is placed between the heating pad and the cooling plate to minimize contact resistance. All external surfaces of the cooling plates and piping are insulated to minimize heat exchange with the surroundings, ensuring the accuracy of the experimental measurements. The system is charged with R134a as the working refrigerant.
The experimental setup is equipped with a comprehensive array of sensors for data acquisition. Eight K-type thermocouples are strategically placed on each of the four cooling plates to measure surface temperature distribution. Pressure transducers are installed at the inlet and outlet of each cooling plate to measure the pressure drop. Additional pressure and temperature sensors are positioned at the compressor inlet and discharge to monitor the system’s operational state. A smart power meter is used to measure the power consumption of the compressor and fans. All data are collected using an Agilent 34972A data logger and transmitted to a host computer via RS485 communication protocol, where it is processed using NI LabVIEW and Python. All tests are conducted at an ambient temperature of 25°C. For each experimental condition, the system is allowed to stabilize for 15 minutes before data recording, and all data are recorded over a 30-minute steady-state period.
Data Reduction and Uncertainty Analysis
To evaluate the performance of the direct cooling thermal management system for energy storage batteries, several key parameters are derived from the raw experimental data. The average temperature of a single cooling plate is calculated as the arithmetic mean of the eight temperature measurement points:
$$ T_{ave} = \frac{1}{8} \sum_{i=1}^{8} T_i \tag{1} $$
where \( T_{ave} \) is the average surface temperature of a single cold plate in °C, and \( T_i \) is the temperature at individual measurement point \( i \). The maximum temperature difference on a single cold plate, which is an indicator of its surface temperature uniformity, is defined as:
$$ \Delta T_{max} = \max(T_i) – \min(T_i) \tag{2} $$
where \( \Delta T_{max} \) represents the maximum temperature difference on a cold plate in °C, and \( \max(T_i) \) and \( \min(T_i) \) are the highest and lowest temperatures measured on that plate, respectively.
The pressure loss across each cooling plate is determined by the difference between the inlet and outlet pressures. To normalize this parameter and assess its relative impact, a pressure loss ratio is defined:
$$ \Delta p = p_{in} – p_{out} \tag{3} $$
$$ \phi_{loss} = \frac{\Delta p}{p_{in}} \times 100\% \tag{4} $$
Here, \( \Delta p \) is the pressure drop across the cooling plate in kPa, \( p_{in} \) and \( p_{out} \) are the refrigerant pressures at the inlet and outlet of the cold plate in kPa, respectively, and \( \phi_{loss} \) is the pressure loss ratio.
The total cooling capacity of the system is assumed to be equal to the total heat generated by the simulated heat sources, as the system is well-insulated and contact resistances are minimized. The system’s coefficient of performance (COP) is a crucial metric for evaluating its energy efficiency. It is calculated as the ratio of the total cooling capacity to the total power input of the compressor and fans:
$$ Q_T = 4 \cdot Q_s \tag{5} $$
$$ COP = \frac{Q_T}{W_{com} + W_{fan}} \tag{6} $$
In these equations, \( Q_T \) is the total cooling capacity in W, \( Q_s \) is the cooling capacity of a single cold plate in W, \( W_{com} \) is the compressor power consumption in W, and \( W_{fan} \) is the fan power consumption in W.
The uncertainty of the indirectly measured parameters is calculated using the Moffat method. For a function \( f = f(Y_1, Y_2, …, Y_n) \), the uncertainty is given by:
$$ \delta f = \sqrt{ \left( \frac{\partial f}{\partial Y_1} \delta Y_1 \right)^2 + \left( \frac{\partial f}{\partial Y_2} \delta Y_2 \right)^2 + \ldots + \left( \frac{\partial f}{\partial Y_n} \delta Y_n \right)^2 } \tag{7} $$
The calculated uncertainties for the key performance indicators are as follows: 0.5% for the cold plate temperature difference, 1.0% for the pressure loss ratio, and 1.4% for the system COP.
| Test Instrument | Measured Parameter | Range | Accuracy |
|---|---|---|---|
| K-type thermocouple | Cold plate temperature / °C | -200 to 260 | ±0.5% |
| Pt100 resistance | Refrigerant temperature / °C | -50 to 200 | ±0.5°C |
| Pt100 resistance | Ambient temperature / °C | -50 to 200 | ±0.5°C |
| MIK-P300 | Low-side pressure / MPa | -0.1 to 2.5 | ±0.5% |
| MIK-P300 | High-side pressure / MPa | -0.1 to 10.0 | ±0.5% |
| DDSU666 | Compressor power / W | 0 to 99999 | ±1.0% |
Results and Discussion
Temperature Reduction and Uniformity Evaluation
Figure 3 (in the original paper) illustrates the temperature distribution across all 32 measurement points on the four cooling plates and the maximum temperature difference over time during a 1400-second steady-state period. This test is conducted at an ambient temperature of 25°C, with a total heat load of 500 W per cold plate and a compressor frequency of 40 Hz. The data reveals that all temperature measurement points on the cold plates fluctuate within a narrow band of 14.67 to 16.85°C. The maximum temperature difference for a single measuring point over time is controlled within 0.4°C, demonstrating excellent temporal temperature stability. Furthermore, the temperature difference between all measuring points on a single cold plate is maintained between 0.69°C and 1.69°C, indicating superior spatial temperature uniformity on each cold plate. This uniformity is a direct consequence of the isothermal phase-change heat transfer process of the refrigerant within the cold plate channels, which is a defining advantage of direct cooling technology for energy storage battery thermal management.
For a more detailed analysis, the average surface temperature and the maximum temperature difference for each of the four cold plates are summarized below. The average temperatures of cold plates 1 to 4 are 15.34°C, 15.48°C, 15.62°C, and 15.35°C, respectively. This yields an extremely low average temperature difference of only 0.28°C between the cold plates, underscoring the system’s exceptional ability to maintain uniform temperatures across the entire battery pack. The maximum temperature differences on the individual plates are 0.79°C, 1.31°C, 1.56°C, and 0.85°C, respectively. All of these values are far below the typical industry standard of 5°C for battery pack temperature uniformity, confirming that the direct cooling system can effectively meet and exceed the thermal management requirements for energy storage batteries.
| Cold Plate Number | Average Temperature (°C) | Maximum Temperature Difference (°C) |
|---|---|---|
| 1 | 15.34 | 0.79 |
| 2 | 15.48 | 1.31 |
| 3 | 15.62 | 1.56 |
| 4 | 15.35 | 0.85 |
System Pressure Drop Analysis
The pressure drop of the two-phase refrigerant as it flows through the cooling plates is a critical factor influencing system performance. The heat transfer mechanism is forced convective boiling. In an ideal scenario, the refrigerant pressure would remain constant, and the evaporation temperature would therefore stay constant, resulting in perfect temperature uniformity. However, in practice, frictional and accelerational pressure losses are inevitable. A pressure drop leads to a corresponding decrease in the refrigerant saturation temperature, which can negatively impact the surface temperature uniformity of the cold plate. The experimental data at 500 W heat load and 40 Hz compressor frequency show that the pressure losses across cold plates 1 to 4 are 21.52 kPa, 14.04 kPa, 10.67 kPa, and 4.99 kPa, respectively. The corresponding pressure loss ratios are 5.30%, 3.47%, 2.66%, and 1.26%. Although cold plate 1 exhibits the highest pressure drop, its ratio is still a modest 5.30% of the inlet pressure.
The effect of this pressure drop on the refrigerant evaporation temperature is shown below. The resultant evaporation temperature decreases across cold plates 1 to 4 are 1.62°C, 1.05°C, 0.79°C, and 0.37°C, respectively. The maximum decrease is only 1.62°C. This small temperature glide confirms that the carefully designed cold plate flow channels and the uniform refrigerant distribution at the inlet are highly effective. The system successfully minimizes the temperature non-uniformity that could arise from pressure losses, thereby preserving the inherent advantage of isothermal phase-change cooling. This characteristic is particularly important for large-scale energy storage battery packs, where maintaining a uniform temperature is essential for preventing accelerated aging of individual cells and mitigating the risk of thermal runaway.
| Cold Plate Number | Pressure Loss (kPa) | Pressure Loss Ratio (%) | Evaporation Temperature Drop (°C) |
|---|---|---|---|
| 1 | 21.52 | 5.30 | 1.62 |
| 2 | 14.04 | 3.47 | 1.05 |
| 3 | 10.67 | 2.66 | 0.79 |
| 4 | 4.99 | 1.26 | 0.37 |
System Performance under Variable Compressor Frequency
To investigate the impact of operating parameters on system performance and to identify optimal control strategies, the compressor frequency is varied while maintaining a constant heat load of 500 W per cold plate. The compressor frequency is adjusted to 35, 40, 45, and 50 Hz. As the compressor frequency increases, the refrigerant mass flow rate increases, leading to a lower evaporation temperature in the cold plates. This enhances the system’s cooling capacity, resulting in lower average cold plate temperatures. However, this also leads to higher refrigerant velocities, which can worsen flow distribution and create larger temperature gradients across the cold plates.
The system’s average cold plate temperature and maximum temperature difference as functions of compressor frequency are presented. The average temperatures are 21.03°C, 17.58°C, 15.45°C, and 14.87°C for frequencies of 35, 40, 45, and 50 Hz, respectively. While the average temperature decreases with increasing frequency, the maximum system temperature difference correspondingly increases from 1.13°C to 1.39°C. This indicates a slight degradation in temperature uniformity at higher compressor speeds. Nevertheless, even at the highest frequency tested, the maximum temperature difference of 1.39°C remains significantly below the 5°C threshold, confirming that the system maintains excellent thermal performance across a range of operating conditions.
The compressor compression ratio and the system COP are also analyzed. The compression ratios are measured to be 1.93, 2.28, 2.35, and 2.88 for the compressor frequencies of 35, 40, 45, and 50 Hz, respectively. Concurrently, the system COP decreases progressively from 8.16 to 5.24. This decline in COP can be directly attributed to the increased compressor work required to achieve a higher compression ratio. At a constant thermal load, the higher compressor power consumption results in a lower system energy efficiency. The experimental data highlights a critical trade-off in the operation of direct cooling thermal management systems for energy storage batteries. Higher compressor frequencies provide greater cooling power and lower temperatures, but at the cost of reduced energy efficiency and slightly poorer temperature uniformity.
| Compressor Frequency (Hz) | Average Cold Plate Temperature (°C) | Maximum System Temperature Difference (°C) | Compression Ratio | System COP |
|---|---|---|---|---|
| 35 | 21.03 | 1.13 | 1.93 | 8.16 |
| 40 | 17.58 | 1.14 | 2.28 | 7.09 |
| 45 | 15.45 | 1.21 | 2.35 | 6.24 |
| 50 | 14.87 | 1.39 | 2.88 | 5.24 |
The findings reveal that for the specific low heat load condition of 500 W per cold plate, operating at a lower compressor frequency of 35 Hz is the most advantageous strategy. In this configuration, the system achieves its highest COP of 8.16, which represents a significant improvement in energy efficiency compared to conventional thermal management systems. Importantly, this high efficiency does not compromise thermal performance. The average cold plate temperature is 21.03°C, which falls comfortably within the recommended operating range of 20-40°C for energy storage batteries. The maximum system temperature difference is just 1.13°C, satisfying the stringent temperature uniformity requirement of less than 5°C. This demonstrates that by judiciously selecting the compressor operating frequency, it is possible to achieve both high energy efficiency and excellent thermal control for energy storage battery thermal management.
This analysis indicates that a fixed-speed operation at a lower frequency might be more desirable for this low-load application. However, a variable-frequency drive offers flexibility to adapt to changing thermal loads, such as during fast charging, high ambient temperatures, or battery degradation. For example, during a high-rate charge event, the heat generation rate would increase, and the system could automatically increase the compressor frequency to provide additional cooling capacity. The optimal control strategy would be to operate at the lowest possible compressor frequency that still meets the thermal management requirements, thereby maximizing system COP and minimizing energy consumption. The data from this study provides a robust basis for developing such intelligent control algorithms for energy storage battery thermal management systems.
Conclusion
This experimental study provides a comprehensive evaluation of a direct cooling thermal management system for energy storage batteries under a representative low-heat-load condition. The system demonstrates outstanding temperature control and uniformity capabilities, along with high energy efficiency. The key conclusions derived from this work are as follows:
(1) The direct cooling system exhibits excellent temperature uniformity. At an ambient temperature of 25°C, a heat load of 500 W per cold plate, and a compressor frequency of 40 Hz, the maximum temperature difference on a single cold plate is only 1.56°C. The average temperature difference between the four cold plates is a mere 0.28°C. These values are far below the conventional 5°C threshold, confirming the system’s effectiveness in providing a uniform thermal environment, which is critical for the longevity and safety of energy storage batteries.
(2) The pressure drop characteristics of the cold plates are favorable. The maximum pressure loss across a single cold plate is 21.52 kPa, corresponding to a pressure loss ratio of only 5.30%. This results in a maximum refrigerant evaporation temperature drop of only 1.62°C across the plates. The minimized pressure losses contribute significantly to the system’s superior temperature uniformity.
(3) The compressor operating frequency is a key parameter governing system performance. Increasing the compressor frequency from 35 Hz to 50 Hz lowers the average cold plate temperature from 21.03°C to 14.87°C but also increases the system temperature difference from 1.13°C to 1.39°C. More importantly, the system COP decreases significantly from 8.16 to 5.24 due to the increased compression ratio and compressor power consumption. The optimal operating point in this study is identified at 35 Hz, where the system achieves a maximum COP of 8.16 while maintaining average temperature and maximum temperature difference well within the safe and desirable limits for energy storage battery operation. This underscores the importance of intelligent compressor control for maximizing the energy efficiency of direct cooling thermal management systems in energy storage applications.