Control Strategies for Energy Storage Inverters in Microgrids

Introduction

The rapid integration of renewable energy sources, such as photovoltaic and wind power, into modern power systems has introduced challenges related to grid stability due to their inherent intermittency and low inertia. Energy storage inverters, as critical interfaces between energy storage systems (ESS) and the grid, play a pivotal role in mitigating these challenges. This study focuses on improving the control strategies of energy storage inverters to enhance their voltage and frequency regulation capabilities in microgrid applications. By analyzing traditional droop control and Virtual Synchronous Generator (VSG) control, adaptive control methods are proposed to address transient voltage fluctuations, power angle instability, and frequency oscillations.


Mathematical Modeling of Energy Storage Inverters

Energy storage inverters are classified into voltage-source inverters (VSI) and current-source inverters (CSI). For grid-connected applications, VSIs are preferred due to their stable DC-link voltage and compatibility with LC filters. The three-phase VSI topology is modeled in the dq reference frame to simplify control design. The dynamic equations governing the inverter are:⎩⎨⎧​Lfdtdid​​=ed​−ud​−Rfid​+ωLfiqLfdtdiq​​=eq​−uq​−Rfiq​−ωLfidCfdtdud​​=id​−igd​+ωCfuqCfdtduq​​=iq​−igq​−ωCfud​​

where id​,iq​ and ud​,uq​ represent the dq-axis currents and voltages, ed​,eq​ are the inverter’s internal voltages, and igd​,igq​ denote grid currents.


Traditional Droop Control

Droop control mimics the primary frequency and voltage regulation of synchronous generators. The fundamental equations are:{f=f0​−m(Pe​−P0​)E=E0​−n(Qe​−Q0​)​

Here, m and n are the droop coefficients for active and reactive power, respectively. However, traditional droop control exhibits poor transient performance during large load changes. For instance, simulations reveal a voltage dip of 20% when a 200 kW load is switched (Table 1).

Table 1: Simulation Parameters for Droop Control

ParameterValue
DC-link voltage (Udc​)700 V
Grid voltage (Ug​)380 V (line-to-line)
Filter inductance (Lf​)1 mH
Droop coefficient (m)1.5×10−5
Droop coefficient (n)1×10−5
Load step (1 s)200 kW

Virtual Synchronous Generator (VSG) Control

VSG control emulates the inertia and damping characteristics of synchronous generators. The rotor dynamics and excitation control are modeled as:

Active Power-Frequency Control:Jdtdω​=Pm​−Pe​−D(ωω0​)

Reactive Power-Voltage Control:E=E0​+ki​∫(Q0​−Qe​)dt

where J is the virtual inertia, D is the damping coefficient, and ki​ is the integral gain. VSG outperforms droop control in frequency stabilization due to its inertial support. A comparative simulation shows that VSG reduces frequency deviations by 40% during a 5 kW load step.


Adaptive Droop Control with Hysteresis

To address voltage transient issues in traditional droop control, an ​adaptive reactive current droop strategy is proposed. The droop coefficient n is dynamically adjusted based on the rate of voltage change (dE/dt):ni​={k1​​dtdE​​−1k2​​if ​dtdE​​<Cst​otherwise​

where k1​, k2​, and Cst​ are tuning parameters. Small-signal stability analysis confirms that the adaptive strategy maintains system stability while reducing voltage fluctuations by 30% during load transitions (Table 2).

Table 2: Performance Comparison of Droop Controls

MetricTraditional DroopAdaptive Droop
Voltage dip (200 kW)245 V261 V
Recovery time0.51 s0.04 s
THD under load variation4.8%2.1%

Additionally, a ​hysteresis-based current limiter is integrated to prevent power angle instability during grid faults. By constraining the active current Id​ within ±Δδ, the strategy ensures stable operation during voltage sags.


Adaptive VSG Control and Energy Storage Configuration

Traditional VSG control suffers from power oscillations during primary frequency regulation. To mitigate this, ​dynamic inertia (J) and ​damping (D) are introduced:J=J0​(1+αdtdω​),D=D0​(1+β(ωω0​))

where α and β are adaptation gains. Simulations demonstrate a 50% reduction in power overshoot compared to fixed-parameter VSG (Table 3).

Table 3: VSG Parameter Impact on Frequency Response

ParameterRise Time (s)Overshoot (%)Settling Time (s)
J=0.10.128.20.35
J=0.90.4822.61.12
D=40.2815.30.78
D=150.184.70.41

Furthermore, the energy storage capacity required for VSG-based inertia support is derived as:EESS​=2ηJ(ωmax2​−ωmin2​)​

where η is the efficiency of the energy storage inverter. For a microgrid with J=0.8kg\cdotpm2 and Δω=2rad/s, the minimum storage capacity is 12 kWh.


Conclusion

This study advances the control strategies for energy storage inverters by proposing adaptive droop and VSG algorithms. Key contributions include:

  1. Adaptive Droop Control: Enhances voltage stability during large load changes.
  2. Hysteresis Limiter: Prevents power angle instability under grid faults.
  3. Dynamic VSG Parameters: Suppress frequency oscillations and optimize energy storage sizing.

Future work will explore hybrid control architectures and real-time optimization of adaptation gains for multi-inverter systems.

Scroll to Top